Understanding IAC Operation
4-4
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
4.2.2 Redundant Operation with Maintenance Bypass UPS Mode
The MOBs provide redundant power to the critical load through the MIS. The wraparound
MBP is open.
Figure 4-4 shows the path of electrical power through the IAC during redundant operation
when bypass is in UPS mode.
OUTPUT TO
CRITICAL LOAD
IAC
MIS MBP
MAIN POWER FLOW IN UPS MODE
MAIN POWER FLOW IN MAINTENANCE BYPASS MODE
MOB 1
MOB 2
FROM UPM 1
OUTPUT
FROM UPM 2
OUTPUT
AC INPUT TO
BYPASS FROM
UTILITY
Figure 4-4. Path of Current Through the IAC during Redundant Operation in UPS Mode