3-1
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
Chapter 3 Installing the IAC
3.1 Preliminary Installation Information
WARNING
Installation should be performed only by qualified personnel.
Refer to the following while installing the IAC:
Appendix A contains installation drawings and additional installation notes.
Dimensions are in millimeters and inches.
Do not tilt the cabinets more than 10° during installation.
Remove the conduit landing plates to add conduit landing holes or remove knockouts,
as required. Plate material is 16 gauge steel (1.5 mm/0.060 thick).
Install the cabinets on a level floor suitable for computer or electronic equipment.
See Table A on page A-6 for equipment weight and point loading.
Details about control wiring are provided in each procedure. Drawing 164201590-7 and
Table U through Table W, starting on page A-56, identify the control wiring
terminations.
Refer to the applicable Powerware 9390 Installation and Operation manual, listed in
paragraph 1.5, for UPS cabinet installation, wiring information, and conduit and terminal
locations.
3.2 Unloading the Powerware 9390 IAC from the Pallet
The IAC is bolted to a wooden pallet supported by wood skids. To remove the pallet,
perform the following procedure:
WARNING
The IAC is heavy. See Table A on page A-6 for weight of cabinets. If unloading instructions are
not closely followed, the cabinet may cause serious injury.
CAUTION
Donottiltcabinetsmorethan10° from vertical.