7-1
EATON Powerware
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
Chapter 7 Product Specifications
7.1 Model Number
The IAC is housed in a free -standing cabinet with safety shields behind the doors.
System Model Frequency
Powerware 9390 IAC -B and IAC -T 50/60 Hz
7.2 IAC Input
Operating Input Voltage
(Nominal +10/–15%)
208 Vac nominal (50/60 Hz)
480 Vac nominal (50/60 Hz)
Operating Input
Frequency Range
¦5Hz
Operating Input Current
See Appendix A: Table D throughTable I
7.3 IAC Output
Operating Output Voltage
(Nominal +10/–15%)
208 Vac nominal (50/60 Hz)
480 Vac nominal (50/60 Hz)
Operating Output
Frequency Range
¦5Hz
Output Current
See Appendix A: Table D through Table I
7.4 Environmental Specifications
Operating Temperature
0 to 40°C (32–104°F) without derating. The recommended
operating temperature is 25°C (77°F).
Operating Altitude
Maximum 1500m (5000 ft) at 40°C without derating
Storage Temperature
–25 to +60°C
Relative Humidity
(Operating and Storage)
5% to 95% maximum noncondensing
Acoustical Noise
N/A
EMI Suppression
N/A
Electrostatic Discharge
(ESD) Immunity
N/A