POWER WIRING INSTALLATION NOTES
013106B
164201590---4
5of13
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
Installation Information
A-23EATON Powerwar e
®
9390 IAC-B and IAC-T Installation and Operation Manual S 164201590 Rev C powerware.com
Ta b l e I . INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9390 IAC 100–160 kVA 480V
(1+1 Parallel Redundant Configuration with Maintenance Bypass)
Units Rating 50/60 H z
Basic Unit Rating
KVA 100 120 160
Input and Bypass Input
Output
VOLTS
VOLTS
480
480
480
480
480
480
AC Input from UPM
(Standalone Installation)
F ull Load Current for each Modul e
(3) Phases, (1) Ground
D
AMPS 120 144 192
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
For contractor-supplied wiring, refer to the applicable
Powerware 9390 UPS Installation and Operation manual,
listed in paragraph 1.5. Wiring for li n e-up -a nd-m at ch
installation is factory-supplied.
AC Input to Maintenance Bypass
(Line- up- and- Mat c h or Standal one Inst al l ati o n)
(3) Phases, (1) Neutral---if required, (1) Ground
E
AMPS 120 144 192
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
4/0
(1)
4/0
(1)
1/0
(2)
AC Output to Critical Load
(Line- up- and- Mat c h or Standal one Inst al l ati o n)
Full Load Current
(3) Phases, (1) Ground
F
AMPS 120 144 192
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
4/0
(1)
4/0
(1)
1/0
(2)
NOTE: Callout letters D, E, and F map to drawing 164201590 ---3, sheet 11 of 11.