Technical Data
For more information visit: www.EatonElectrical.comMN05013003E 265
EZ512-DC-…, EZ6..-DC-.E, EZ7..-DC--
Status display LCD (if provided) LCD (if provided)
Electrical isolation
To power supply No No
Between each other No No
To the outputs
Yes Yes
Rated voltage
Rated value 12 V DC 12 V DC
0 signal
4 V DC (I1 to I8) 4 V DC (I1 to I12)
1 signal
8 V DC (I1 to I8) 8 V DC (I1 to I12)
Input current on 1 signal
3.3 mA at 12 V DC
(I1 to I6)
3.3 mA at 12 V DC
(I1 to I6, I9 to I12)
I7, I8
1.1 mA at 12 V DC 1.1 mA at 12 V DC
Delay time for 0 to 1
Debounce ON
20 ms 20 ms
Debounce OFF
Normally 0.3 ms (I1 to I16)
Normally 0.35 ms (I7, I8)
Normally 0.3 ms (I1 to I6, I9, I10)
Normally 0.35 ms (I7, I8, I11,
I12)
Delay time for 1 to 0
Debounce ON
20 ms 20 ms
Debounce OFF
Normally 0.3 ms (I1 to I16)
Normally 0.15 ms (I7, I8)
Normally 0.4 ms
(I1 to I6, I9 to I10)
Normally 0.2 ms (I7, I8, I11, I12)
Cable length (unshielded)
100 m 100 m
EZ512-DA-… EZ719-DA-…
EZ512-DC-… EZ6..-DC-.E EZ7..-DC-…
Digital inputs
Number
8 12 12
2 inputs (I7, I8)
usable as analog
inputs
4 inputs (I7, I8, I11, I12)
usable as analog inputs