Counters
For more information visit: www.EatonElectrical.comMN05013003E 117
Parameter display in RUN mode:
Retention
Counter relays can be operated with retentive actual values.
You can select the retentive counter relays in the SYSTEM…
J RETENTION… menu. C5 to C7, C8 and C13 to C16 can
be selected.
If a counter relay is retentive, the actual value is retained when
the operating mode changes from RUN to STOP as well as
when the power supply is switched off.
When EZ is restarted in RUN mode, the counter relay
continues with the retentively stored actual value.
Determining counter frequency
The maximum counter frequency depends on the length of the
circuit diagram in EZ. The number of contacts, coils and rungs
used determines the run time (cycle time) required to process
the EZ circuit diagram.
Example: When using EZ512-DC-TC with only three rungs for
counting, resetting and outputting the result via the output, the
counter frequency may be 100 Hz.
The maximum counter frequency depends on the maximum
cycle time.
The following formula is used to determine the maximum
counter frequency:
f
c
= maximum counter frequency
t
c
= maximum cycle time
0.8 = Correction factor
Current setpoint, constant (0309)
# Contact has not switched.
â Contact has switched.
Actual value (00042)
C1 N +
S 00309
# C:00042
f
c
=
1
× 0.8
2 ×
t
c