In RUN mode EZ operates with a new setpoint as soon as it
has been modified in the parameter display and saved with
OK.
Example: Changing switch times for outdoor lighting
The outdoor lighting of a building is automatically switched on
from 19:00 to 23:30 Mondays to Fridays in the EZ circuit
diagram.
The parameter set for the time switch function relay 1 is saved
in channel A and looks like this.
From the following weekend, the outdoor lighting is now also
required to switch on between 19:00 and 22:00 on Saturdays.
XSelect PARAMETER from the main menu.
The first parameter set is displayed.
XUse Í or Ú to scroll through the parameter sets until
channel A of time switch 1 is displayed.
XPress Í to select the next empty parameter set, in this
case channel B of time switch 1.
The current time is 15:21.
XChange the value for the day interval from MO to SA:
úí Move between the parameters
ÍÚ Change value.
XPress OK to acknowledge the value SA.
XChange the ON value to 19:00.
XMove to the value of ON
XPress OK.
úí Move between the parameters
ÍÚ Change value.
XPress OK to acknowledge the value 19:00.
Ö1 A 15:21 +
D MO-FR
ON 19:00
OFF 23:30
Ö1 B 15:21 +
D --
ON 00:00
OFF 00:00
Ö1 B 15:21 +
D SA
ON 00:00
OFF 00:00
Ö1 B 15:21 +
D SA
ON 19:00
OFF 00:00