Connecting the outputs
For more information visit: www.EatonElectrical.comMN05013003E 55
EZ620-..-TE
Figure 30: EZ620-..-TE transistor outputs
Parallel connection:
Up to four outputs can be connected in parallel in order to
increase the power. The output current will increase in this
case to a maximum of 2 A.
0 V H
S1 S2 S3 S4 S5 S6 S7 S8 +24 V
f 2.5 A
F10 A
0V
+ 24 V H
R
5 W/24 V
0.5 A
(20.4 – 28.8 V H)
24 V H
0.5 A
Q
Q
Caution!
Outputs may only be connected in parallel within a group
(Q1 to Q4 or Q5 to Q8, S1 to S4 or S5 to S8), such as Q1
and Q3 or Q5, Q7 and Q8. Outputs connected in parallel
must be switched at the same time.
Caution!
Please note the following when switching off inductive
loads.
Suppressed inductive loads cause less interference in the
entire electrical system. For optimum suppression the
suppressor circuits are best connected directly to the
inductive load.
EZ500_700.book Page 55 Tuesday, May 3, 2005 5:15 PM