Terminals
For more information visit: www.EatonElectrical.comMN05013003E 33
XOpen the EZ-LINK connections on the side of both EZ
devices.
XFit the EZ-LINK data connector EZ-LINK-DS in the opening
provided on the expansion device.
XPlug the devices together.
XProceed in the reverse order to dismantle the device.
Terminals Tools
Slot-head screwdriver, width 3.5 mm, tightening torque
0.6 Nm.
Cable cross-sections
Solid: 0.2 to 4 mm
2
Flexible with ferrule: 0.2 to 2.5 mm
2
Connecting the power
supply
Cable protection
Connect on EZ cable protection (F1) rated for at least 1 A
(slow).
J
The required connection data for device types, EZ-AB with
24 V AC, EZ-AC with standard voltages of 100 V AC, EZ-
DA with 12 V DC and EZ-DC with 24 V DC are provided in
the section “Technical Data”, page 258.
The EZ500 and EZ700 basic units run a system test for two
seconds after the power supply has been switched on.
Either RUN or STOP mode will be activated after these two
seconds, depending on the default setting.