Wiring with EZ
MN05013003E144
Figure 62: Time overlaps signal diagram
Power failure example
The power is removed between 15:00 and 17:00. The relay
drops out and remains off, even after the power returns, since
the first off time was at 16:00.
24 hour switching example
The time switch is to switch for 24 hours. On time at 0:00 on
Monday and off time at 0:00 on Tuesday.
J
On and off times always follow the channel which switches
first.
Ö4 A +
D MO-SU
ON 12:00
OFF 16:00
Ö4 B +
D MO-SU
ON 12:00
OFF 18:00
J
When it is switched on, EZ always updates the switching
state on the basis of all the available switching time
settings.
Ö1 A +
D MO
ON 00:00
OFF --:--
Ö1 B +
D TU
ON --:--
OFF 00:00