EZ512-DA-…, EZ719-DA-...
Input current with 1 signal
R1 to R12, I1 to I6
(EZ71. also I9 to I12)
6 × 0.5 mA at 230 V AC 50 Hz,
6 × 0.25 mA at 115 V AC 60Hz
10 × (12) 0.5 mA at 230 V AC,
50 Hz
10 × (12) × 0.25 mA at
115 V AC, 60 Hz
Input current on 1 signal
I7, I8
2 × 6 mA at 230 V AC 50 Hz,
2 × 4 mA at 115 V AC 60 Hz
2 × 6 mA at 230 V AC 50 Hz,
2 × 4 mA at 115 V AC 60 Hz
Delay time for 0 to 1 and 1 to 0 for I1 to I6, I9 to I12
Debounce ON
80 ms (50 Hz), 66
2
/3 ms (60 Hz) 80 ms (50 Hz), 66
2
/3 ms (60 Hz)
Debounce OFF (also R1 to
R12)
20 ms (50 Hz), 16
2
/3 ms (60 Hz) 20 ms (50 Hz), 16
2
/3 ms (60 Hz)
Delay time I7, I8 for 1 to 0
Debounce ON
160 ms (50 Hz), 150 ms (60 Hz) 80 ms (50 Hz),66
2
/3 ms (60 Hz)
Debounce OFF
100 ms (50 Hz/60 Hz) 20 ms (50 Hz), 16
2
/3 ms (60 Hz)
Delay time I7, I8 for 0 to 1
Debounce ON
80 ms (50 Hz), 66
2
/3 ms (60 Hz) 80 ms (50 Hz), 66
2
/3 ms (60 Hz)
Debounce OFF
20 ms (50 Hz), 16
2
/3 ms (60 Hz) 20 ms (50 Hz), 16
2
/3 ms (60 Hz)
Max. permissible cable length (per input)
I1 to I6, R1 to R12
(with EZ719-.. also I9 to I12)
Normally 40 m Normally 40 m
I7, I8
Normally 100 m Normally 100 m
EZ-512-AC-… EZ618-AC-.E, EZ719-AC-...
EZ512-DA-… EZ719-DA-…
Digital inputs
Number
8 12
2 inputs (I7, I8) usable as
analog inputs
4 inputs (I7, I8, I11, I12) usable
as analog inputs