For more information visit: www.EatonElectrical.com
Inside EZ
MN05013003E240
These modules offer considerably more functions than simple
I/O expansion modules. Depending on type, all the data of the
program can be read and setpoints can be written. The
functions of the individual devices are described in the
relevant documentation.
How is an expansion unit recognized
EZ checks cyclically whether a device is sending data on
EZ-LINK.
Transfer behavior
The input and output data of the expansion units is transferred
serially in both directions. Take into account the modified
reaction times of the inputs and outputs of the expansion
units:
Input and output reaction times of expansion units
The debounce setting has no effect on the expansion unit.
Transfer times for input and output signals:
• Local expansion
Time for inputs R1 to R12:
30 ms + 1 cycle
• Time for outputs S1 to S6 (S8):
15 ms + 1 cycle
• Remote expansion
Time for inputs R1 to R12:
80 ms + 1 cycle
• Time for outputs S1 to S6 (S8):
40 ms + 1 cycle