Eaton PROFIBUS-DP EZ204-DP User Manual Page 154

  • Download
  • Add to my manuals
  • Print
  • Page
    / 300
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 153
For more information visit: www.EatonElectrical.com
Wiring with EZ
MN05013003E150
Timing relays EZ provides 16 timing relays T1 to T16 for use as required.
A timing relay is used to change the switching duration and the
make and break times of a switch contact. The delay times
can be configured between 2 ms and 99 h 59 min. You can
use positive values, values of analog inputs, actual values of
counter relays and timing relays.
You can also use EZ as a multi-function relay in the
application. EZ is more flexible than any hard-wired timing
relay since you can wire all the functions at the push of a
button as well as program additional functions.
You integrate a timing relay into your circuit in the form of a
contact and coil.
Parameter display and parameter set for a timing relay:
J
The “flash” function starts on EZ500 and EZ700 with the
pulse. If required, the same timing relays can also be used
for retentive data.
I1-I4----TT1
T1-------ÄQ3
Contact Coil
T1 to T16 Contact of a timing relay
TT1 to TT16 Enable, timing relay trigger
RT1 to RT16 Reset coil of the timing relay
HT1 to HT16 Stop coil of the timing relay
(H = Stop , S means the Set coil
function)
J
To prevent unpredictable switching states, use each coil of
a relay once only in the circuit diagram.
T1 X S +
I1 00.000
I2 00.000
T:
T1 Timing relay number 1
X On-delayed mode
S Time range in seconds
+ + appears in the PARAMETER menu.
- does not appear in the PARAMETER menu.
EZ500_700.book Page 150 Tuesday, May 3, 2005 5:15 PM