Page view 148
Operating hours counter
For more information visit: www.EatonElectrical.comMN05013003E 145
Operating hours counter EZ provides 4 independent operating hours counters. These
operating hours counters enable you to record the operating
hours of systems, machines and machine parts. An adjustable
setpoint can be selected within the value range. In this way,
maintenance times can be logged and reported. The counter
states are retained even when the device is switched off. As
long as the count coil of the operating hours counter is active,
EZ counts the hours in second cycles.
You integrate an operating hours counter into your circuit in
the form of a contact and coil.
Parameter display and parameter set for the operating hours
counter function block:
In the parameter display of an operating hours counter you
change the setpoint in hours and the enable of the parameter
display.
I2-------ÄO1
O1uI8----RO1
h------TT1
T1-------ÄQ3
Contact Coil
O1 to O4
ÄO1 to ÄO4 Count coil of the operating hours
counter
RO1 to RO4 Reset coil of the operating hours
counter
O4 +
S 000000
O:
O4 Operating hours counter number 4
+ + appears in the parameter display
- appears in the parameter display
S Setpoint in hours
O: Actual value of the operating hours counter in hours [h]