Page view 117
Troubleshooting Charts Using Fault Codes
108 9000X AF Drives MN04001004E—May 2011 www.eaton.com
F45—DevParAdded
F50—Analog Input I
in
<4 mA
F45
Reset the fault
Clear fault memory
Note: F45 should appear when different type
option board has been added
Note: Faulty board is displayed
on panel bottom line
A = Slot A
B = Slot B
C = Slot C
D = Slot D
E = Slot E
Measured value =
Monitored value?
No
Y
es
Measure mA signal of
the measurement device
Y
es
Test input on the option board, if faulty
replace option board with functioning one
I<4mA?
No
Make corrections to external circuit
Test and/or replace control board
with functioning one according to
instructions in service manual.
Replace defective parts as
recommended in spare parts lists
F50
Check value on monitoring
page corresponding to the input
Clear fault memory
Page view 117