Eaton SPI9000 User Manual Page 69

  • Download
  • Add to my manuals
  • Print
  • Page
    / 136
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 68
Technical Data
9000X AF Drives MN04001004E—May 2011 www.eaton.com 59
Specifications
SVX9000/SPX9000 Drive Specifications
Description Specification
Power Connections
Input voltage (V
in
) 208–240V +10%/–15%
380–500V +10%/–15%
525–690V +10%/–15%
Input frequency (f
in
) 50/60 Hz (variation up to 45–66 Hz)
Connection to utility power Once per minute or less (typical operation)
Maximum symmetrical supply current 208–240V, 100 kAIC
380–500V, 100 kAIC
525–690V, 100 kAIC
Motor Connections
Output voltage 0 to V
in
Continuous output current Ambient temperature max. 122°F (50°C), overload 1.5 x I
H
(1 min. out of 10 min.)
Starting current 200% for 2 seconds
Output frequency 0 to 320 Hz standard (optional frequencies available)
Frequency resolution 0.01 Hz
Control Characteristics
Control method SVX frequency control (V/f)
SVX open loop sensorless vector
SPX open loop sensorless vector control
SPX closed loop control
Switching frequency Adjustable with parameter 2.6.9
208–230V: 3/4–15 hp: 1 to 16 kHz; 20–30 hp: 1 to 6 kHz
380–500V: 1–30 hp: 1 to 16 kHz; 40–200 hp: 1 to 6 kHz
525–690V: All sizes: 1 to 6 kHz
Frequency reference Analog input: resolution 0.1% (10-bit), accuracy ±1%
Panel reference: resolution 0.01 Hz
Field weakening point 30 to 320 Hz
Acceleration time 0.1 to 3000 sec.
Deceleration time 0.1 to 3000 sec.
Braking torque DC brake: 15% to 150% x T
n
(without brake option)
Environment
Ambient operating temperature 14°F (–10°C), no frost to 122°F (50°C) I
H
14°F (–10°C), no frost to 104°F (40°C) I
L
Storage temperature –40°F (–40°C) to 158°F (70°C)
Relative humidity 0 to 95% RH, noncondensing, noncorrosive, no dripping water
Air quality Chemical vapors: IEC 60721-3-3, unit in operation, Class 3C2
Mechanical particles: IEC 60721-3-3, unit in operation, Class 3S2
Altitude 100% load capacity (no derating) up to 3300 ft (1000m); 1% derating for each
330 ft (100m) above 3300 ft (1000m); max. 10,000 ft (3000m)