Mounting
4 9000X AF Drives MN04001004E—May 2011 www.eaton.com
Environmental Requirements
Ensure that the environment meets the requirements listed
in the table on Pages 59 and 60 for any storage or
operating situation.
The table below specifies the minimum airflow required in
the area where the drive will be mounted.
Cooling Airflow Requirements
Standard Mounting Instructions
1. Measure the mounting space to ensure that it allows
for the minimum space surrounding the drive. Drive
dimensions are in “Dimensions” starting on Page 64.
2. Make sure the mounting surface is flat and strong
enough to support the drive, is not flammable, and is
not subject to excessive motion or vibration.
3. Ensure that the minimum airflow requirements for
your drive are met at the mounting location.
4. Mark the location of the mounting holes on the
mounting surface, using the template provided on
the cover of the cardboard shipping package.
5. Using fasteners appropriate to your drive and mounting
surface, securely attach the drive to the mounting
surface using all four screws or bolts.
Drive Type Cooling Air Required
230V, 3/4–3 hp I
H
41 cfm (70 m
3
/h)
480V, 1–5 hp I
H
230V, 5–7-1/2 hp I
H
112 cfm (190 m
3
/h)
480V, 7-1/2–15 hp I
H
230V, 10–15 hp I
H
250 cfm (425 m
3
/h)
480V, 20–30 hp I
H
575V, 2–25 hp I
H
230V, 20–30 hp I
H
250 cfm (425 m
3
/h)
480V, 40–60 hp I
H
575V, 30–40 hp I
H
480V, 75–125 hp I
H
383 cfm (650 m
3
/h)
575V, 60–75 hp I
H
480V, 150–200 hp I
H
765 cfm (1300 m
3
/h)
575V, 100–150 hp I
H
480V, 250–350 hp I
H
1530 cfm (2600 m
3
/h)
575V, 200–300 hp I
H
480V, 400–550 hp I
H
2295 cfm (3900 m
3
/h)
575V, 400–500 hp I
H
480V, 600–700 hp I
H
3060 cfm (5200 m
3
/h)
575V, 550–700 hp I
H