Fault and Warning Codes
9000X AF Drives MN04001004E—May 2011 www.eaton.com 83
Fault Codes, continued
Fault Code Fault Possible Cause Solution
29** Thermistor fault The thermistor input of an option board has detected
a high motor temperature
Check the motor cooling and the motor loading
Check the thermistor connection
(If the thermistor input of an option board is not being
used, it must be short-circuited)
31 IGBT temperature (hardware) IGBT inverter bridge overtemperature protection has
detected a high short-term overload current
Check loading
Check motor size
32 Fan cooling The SVX9000/SPX9000 cooling fan did not start when
commanded
Contact your Eaton distributor
34 CAN bus communication Sent message not acknowledged Ensure that there is another device on the bus with
the appropriate configuration
36 Control unit The control unit cannot control the power unit and
vice-versa
Change the control unit
37* Device change
(same type)
Option board changed
Different power rating of drive
Reset
No Fault Time Data Record is made
38* Device added
(same type)
Option board added
Drive of different power rating added
Reset
No Fault Time Data Record is made
39* Device removed Option board removed
Drive removed
Reset
No Fault Time Data Record is made
40 Device unknown Unknown option board or drive Contact your Eaton distributor
41 IGBT temperature IGBT inverter bridge overtemperature protection has
detected a high short-term overload current
Check loading
Check motor size
42** Brake resistor
overtemperature
Brake resistor overtemperature protection has
detected excessive braking
Set the deceleration time longer
Use an external brake resistor
43 Encoder fault Exceptional fault data record, see the Active Fault
Menu and Fault Time Data Record for more
information. Additional codes:
1 = Encoder 1 channel A is missing
2 = Encoder 1 channel B is missing
3 = Both encoder 1 channels are missing
4 = Encoder reversed
Check encoder channel connections
Check the encoder board
44* Device change
(different type)
Option board changed
Different power rating of drive
Reset
No Fault Time Data Record is made
Application parameter values restored to default
45* Device added
(different type)
Option board added
Drive of different power rating added
Reset
No Fault Time Data Record is made
Application parameter values restored to default
50** Analog input I
in
<4 mA
(for the signal range
4 to 20 mA)
Current at the analog input is <4 mA
Control cable is broken or loose
Signal source has failed
Check the current loop, signal source, and wiring
51 External fault Digital input set as an external fault input has been
triggered
Check source of trigger
52 Keypad communication fault The connection between the control keypad and the
SVX9000/SPX9000 has been lost
Check the keypad connection and keypad cable
53 Communication bus fault The data connection between the communication bus
master and the communication bus board has failed
Check installation
If installation is correct contact your Eaton distributor
54 Slot fault Defective option board or slot Check that the board is properly installed and seated
in slot. If the installation is correct, contact your Eaton
distributor
56 PT100 board temperature
fault
Temperature limit values set for the PT100 board
parameters have been exceeded
Determine the cause of the high temperature