COMMUNICATION
EATON Powerware
®
9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 2 www.powerware.com
12-6
12.4 Terminal Mode
In this mode, system events are continually logged through the serial port to the
device connected to the port. Port 2 operates by default in Terminal mode.
The Event History Log entries contain a time and date stamp and the alarm text
message. Terminal mode uses this format for printing alarm entries:
MMM DD HH:MM:SS.hh KYWD MESSAGE :::: <CR> <LF>
Symbol Description
MMM Month (3 letters)
DD Day (2 digits)
HH Hour (2 digits)
MM Minute (2 digits)
SS Second (2 digits)
hh Hundredths of Second (2 digits)
KYWD Keyword (ALARM, NOTICE, COMMAND, or STATUS)
:::: System Diagnostic Information
<CR> Carriage Return Character (ASCII 13)
<LF> Line Feed (ASCII 10)
An alarm message is prefixed by the word CLEAR whenever an alarm is entered into
the Event History Log with a cleared status.
12.4.1 Printing Selected Information
NOTE To use a key combination, hold down the Control key and press the letter key.
If a port is operating in Terminal mode and is connected to a computer, use the
following key combinations at any time to print selected information:
[Ctrl]+[P] Prints the entire log with a header
[Ctrl]+[M] Prints the current system meters with a header
[Ctrl]+[A] Prints all system information
[Ctrl]+[B] Prints Battery Test Log