PRODUCT SPECIFICATIONS
EATON Powerware
®
9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 2 www.powerware.com
14-2
14.3 UPS System Output
DC Filtering Ripple voltage less than 0.5% peak to peak
UPS Output Capacity 100% rated current at 0.8 power factor or 100% rated current at 0.9 power
factor
Output Voltage Regulation 1% (10% to 100% load)
Output Voltage
Adjustment
(Nominal +/–5%)
600 Vac nominal, adjustable from 570 Vac to 630 Vac (60 Hz only)
480 Vac nominal, adjustable from 456 Vac to 504 Vac (60 Hz only)
400 Vac nominal, adjustable from 380 Vac to 420 Vac (50/60 Hz)
Output Voltage Harmonic
Content
3% max THD, 2% max single (linear load)
Output Voltage Balance 3% for 100% maximum load imbalance (linear load)
Output Voltage Phase
Displacement
3° for 100% maximum load imbalance (linear load)
Output Transients
"5% for 100% load step or removal
Frequency Regulation
"0.01 Hz free running
Synchronous to Bypass Bypass within voltage limits of +5%, –8% of output setting; bypass within
"0.5 Hz
Frequency Slew Rate 1 Hz per second maximum (adjustable)
Overload Capability 125% for 10 minutes
150% for 10 seconds
Maximum Output
Capability
300% peak for 10 cycles without bypass
14.4 Environmental Specifications
Operating Temperature 0 to 40°C (32–104°F) without derating. The recommended operating
temperature is 25°C (77°F).
Operating Altitude Maximum 1500m (5000 ft) at 40°C without derating
Storage Temperature –20 to +70°C (prolonged storage above 40°C will cause rapid battery
self‐discharge)
Relative Humidity
(Operating and Storage)
95% maximum noncondensing
Acoustical Noise 75 dBA at a 1m distance
Electrostatic Discharge
(ESD) Immunity
Meets IEC 801‐2 specifications.