INSTALLATION REFERENCE
EATON Powerware
®
9315 UPS (500–750 kVA) Installation and Operation Manual S 164201691 Rev 2 www.powerware.com
A-18
Table J. Recommended Installation Parts and Tool (Not Supplied by Eaton)
Part Size Quantity Manufacturer Part Number Notes
Long Barrel 2 Hole Lug 500 MCM
As required
Thomas & Betts 54876BE
Color Code: Brown
Die Code: 87
Bolt, Grade 5 1/2 2
1
N/A N/A
Quantity per lug hole
Flat Washer 1/2
1
N/A N/A
Lock Washer 1/2
1
N/A N/A
Nut 1/2
1
N/A N/A
Manual Hydraulic Crimp Tool 14 Ton 1 Thomas & Betts TBM14M
Die Set N/A 1 Thomas & Betts 15506
13. Standard breakers used in the UPS are rated for 65 KAIC, with optional
breakers rated for 100 KAIC. To prevent cable whipping, secure cables as
shown in Figure A‐10. Wrap line cables together with nominal 9.5 mm (3/8 )
nylon rope or rope having a minimum tensile strength of 8896 N (2000
pounds). Wrap line cables at 152 mm (6 ) and 1305 mm (2 ) from the line
terminals with 5 wraps. Wrap each additional 152.4 mm (6 ) interval with
5 wraps or 25.4 mm (1 ) intervals with 1 wrap.
152 MM [6 INCHES]
NYLON ROPE -9 MM [3/8
INCH] DIAMETER.
MINIMUM OF FIVE WRAPS.
Figure A‐10. Securing Cables