SPI9000 Inverter Unit FR4 – FR8 User Manual
MN04004003E
For more information visit: www.EatonElectrical.com 6-3
April 2006
● Check in Monitoring Menu M1 that the value of Output Frequency changes
according to the change of frequency reference.
● Press the STOP button on the keypad.
9. Run the start-up tests without the motor being connected to the process. If this is not
possible, make sure that running each test is safe prior to running it. Inform your co-
workers of the tests.
● Switch off the DC supply voltage and wait until the drive has stopped as advised on
Page 6-1, Safety Precautions.
● Connect the motor cable to the motor and to the motor cable terminals of the
inverter.
● Make sure that all Start/Stop switches are in Stop positions.
● Switch the supply voltage ON.
● Repeat test 8A or 8B.
10. Connect the motor to the process (if the start-up test was run without the motor being
connected)
● Before running the tests, make sure that this can be done safely.
● Inform your co-workers of the tests.
● Repeat test 8A or 8B.