SPI9000 Inverter Unit FR4 – FR8 User Manual
3-8 For more information visit: www.EatonElectrical.com
MN04004003E
April 2006
Cable Installation and the UL Standards
To meet the UL (Underwriters Laboratories) regulations, a UL-approved copper cable with a
minimum heat-resistance of +60/75°C must be used.
The tightening torques of the terminals are given below in Table 3-8.
Table 3-8: Tightening Torques of Terminals
Tightening torque of terminal connection to the isolative base in in-lb.
Cable and Motor Insulation Checks
1. Motor cable insulation checks
Disconnect the motor cable from terminals U, V and W of the inverter and from the
motor. Measure the insulation resistance of the motor cable between each phase
conductor as well as between each phase conductor and the protective ground
conductor.
The insulation resistance must be >1MΩ.
2. DC supply cable insulation checks
Disconnect the DC supply cable from terminals B- and B+ of the inverter and from DC
supply. Measure the insulation resistance between each conductor and ground.
The insulation resistance must be >1MΩ.
3. Motor insulation checks
Disconnect the motor cable from the motor and open the bridging connections in the
motor connection box. Measure the insulation resistance of each motor winding. The
measurement voltage must equal at least the motor nominal voltage but not exceed
1,000V.
The insulation resistance must be >1MΩ.
Inverter Voltage Frame
Tightening Torque
(in-lb)
SPI003 – 023 480V FR4 4.4 – 5.3
SPI031 – 046
SPI003 – 027
480V
690V
FR6 65
SPI061 – 087
SPI034 – 062
480V
690V
FR7 65
SPI105
SPI052 – 080
480V
690V
FR8 177/80