24 Contactors and Overload Relays PG03407001U – June 2006
Contactors and Overload Relays
The factory assembled reversing contactor for the 40 – 150A devices includes: (2) XTCE…00_
Contactors and (2) XTCEXFBG11 1NO-1NC Seq. B Front Mount Auxiliary Contacts and (1)
XTCEXML_Mechanical Interlock.
1)
Underscore (_) indicates coil suffix required.
The factory assembled reversing contactor for the 40 – 150A devices includes: (2) XTCE…00_
Contactors and (2) XTCEXFBG11 1NO-1NC Seq. B Front Mount Auxiliary Contacts and (1)
XTCEXML_Mechanical Interlock.
1)
Underscore (_) indicates coil suffix required.
XTCR095F11
3 Pole Contactors, Frame F, Reversing
I
e
(A) Maximum kW Ratings AC-3 Spare Auxiliary
Contacts
Eaton
list number
1)
AC-3 3-Phase Motors 50 – 60 Hz K1M K2M
220/
230V
380/
400V
415V 660/
690V
80 25 37 48 63 XTCR080F11_
95 30 45 57 75 XTCR095F11_
XTCR150G11
3 Pole Contactors, Frame G, Reversing
I
e
(A) Maximum kW Ratings AC-3 Spare Auxiliary
Contacts
Eaton
list number
1)
AC-3 3-Phase Motors 50 – 60 Hz K1M K2M
220/
230V
380/
400V
415V 660/
690V
115 37 55 70 90 XTCR115G11_
150 48 75 91 96 XTCR150G11_