124 Technical details PG03407001U – June 2006
Technical details
Coil Data
1)
At 24V: 0.7 – 1.3 without additional auxiliary contact modules and ambient temperature +40°C [104°F].
2)
Coil Suffix AD: U
min
110V DC/U
max
130V DC.
Coil Suffix BD: U
min
200V DC/U
max
240V DC.
Example:
U
C
= 0.7 x U
min
- 1.2 x U
max
U
C
= 0.7 x 24V - 1.2 x 27V DC
Standard, Contactors, Frames B - D, Coil Data
Frame
XTCE007B XTCE009B XTCE012B XTCE015B XTCE018C XTCE025C XTCE032C XTCE040D XTCE050D XTCE065D
Voltage Tolerance
Pick-Up (x U
c
)
AC operated
DC operated
Drop-Out (x U
c
)
AC operated
DC operated
0.8 – 1.1
0.8 – 1.19
1)
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.8 – 1.19
1)
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.8 – 1.19
1)
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.8 – 1.19
2)
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.7 – 1.2
2)
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.7 – 1.2
2)
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.7 – 1.2
2)
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.7 – 1.2
2)
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.7 – 1.2
2)
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.7 – 1.2
2)
0.3 – 0.6
0.15 – 0.6
Power Consumption of the coil at cold state and 1.0 x U
c
AC operated
Pick-Up VA
Pick-Up W
24
19
24
19
24
19
24
19
50
40
52
40
52
40
149
80
149
80
149
80
Single-voltage
coil 50 Hz
Sealing VA
Sealing W
3.4
1.2
3.4
1.2
3.4
1.2
3.4
1.2
7.1
2.1
7.1
2.1
7.1
2.1
16
4.3
16
4.3
16
4.3
60 Hz
Pick-Up VA
Pick-Up W
Sealing VA
Sealing W
30
23
4.4
1.4
30
23
4.4
1.4
30
23
4.4
1.4
30
23
4.4
1.4
67
50
8.7
2.6
67
50
8.7
2.6
67
50
8.7
2.6
178
117
19
5.3
178
117
19
5.3
178
117
19
5.3
50/60 Hz
Pick-Up VA
Pick-Up W
Sealing VA
Sealing W
27
25
22
21
4.2
3.3
1.4
1.2
27
25
22
21
4.2
3.3
1.4
1.2
27
25
22
21
4.2
3.3
1.4
1.2
27
25
22
21
4.2
3.3
1.4
1.2
62
58
48
43
9.1
6.5
2.3
2
62
58
48
43
9.1
6.5
2.3
2
62
58
48
43
9.1
6.5
2.3
2
168
154
120
43
22
14
5.3
4.3
168
154
120
43
22
14
5.3
4.3
168
154
120
43
22
14
5.3
4.3
DC operated
Pick-Up W
Sealing W
3
3
3
3
4.5
4.5
4.5
4.5
12 at 24V
0.5 at 24V
12 at 24V
0.5 at 24V
12 at 24V
0.5 at 24V
12 at 24V
0.5 at 24V
12 at 24V
0.5 at 24V
12 at 24V
0.5 at 24V
Duty Factor (%DF) 100 100 100 100 100 100 100 100 100 100
Switching Time at 100% U
c
(approximate values)
Main Contact
AC operated
Closing delay (mS)
Opening delay (mS)
DC operated
Closing delay (mS)
Opening delay (mS)
<21
<18
<31
<12
<21
<18
<31
<12
<21
<18
<31
<12
<21
<18
<31
<12
<22
<14
<47
<30
<22
<14
<47
<30
<22
<14
<47
<30
<18
<13
<54
<24
<18
<13
<54
<24
<18
<13
<54
<24
Arcing time (mS) 10 10 10 10 10 10 10 10 10 10
Electromagnetic Compatibility (EMC)
Emitted interference To EN-60947-1
Noise Immunity To EN-60947-1
Page view 125