109PG03407001U – June 2006 Technical details
Technical details
1)
Contact Eaton.
Standard Contactors, Frame F - G, Technical Data and Standards
Description XTCE080F XTCE095F XTCE115G XTCE150G
Standards IEC/EN 60947, VDE 0660, UL, CSA, CCC, RoHS
General
Weights in kg
AC operated
DC operated
4.41
4.63
4.41
4.63
4.41
4.63
4.41
4.63
Mechanical Life 10,000 10,000 10,000 10,000
Mechanical Operating Frequency (ops/hr)
AC operated
DC operated
3600
3600
3600
3600
3600
3600
3600
3600
Electrical Operating Frequency (ops/hr)
AC-1; 400V I
e
AC-3; 400V I
e
AC-4; 400V I
e
800
800
300
800
800
300
800
800
300
800
800
300
Climatic Proofing Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60 068-2-30
Insulation Voltage (U
i
) VAC 1000 1000 1000 1000
Impulse Withstand Voltage (U
imp
) VAC 8000 8000 8000 8000
Operational Voltage (U
e
) VAC 1000 1000 1000 1000
Safe Isolation to VDE 0106 Part 101 and Part 101/A1
Between coil and contacts (VAC)
Between contacts (VAC)
690
690
690
690
690
690
690
690
Making Capacity (Amps) 1120 1330 1610 2100
Breaking Capacity (Amps)
220/230V
380/400V
500V
660/690V
1000V
800
800
800
650
1200
950
950
950
800
1200
1150
1150
1150
1100
1200
1500
1500
1500
1200
1200
Short-Circuit Protection Rating Maximum Fuse
Type 2 Coordination
400V; gG/gL 500V
690V; gG/gL 690V
Type 1 Coordination
400V; gG/gL 500V
690V; gG/gL 690V
160
160
250
200
160
160
250
200
250
1)
250
1)
250
1)
250
1)
Degree of Protection IP00
Protection Against Direct Contact when
Actuated from Front (IEC 536)
Finger- and back-of-hand proof
Main Cable Cross-Section
Solid (mm
2
)
————
Flexible with ferrule (mm
2
)
1 x (10 – 95)
2 x (10 – 70)
1 x (10 – 95)
2 x (10 – 70)
1 x (10 – 95)
2 x (10 – 70)
1 x (10 – 95)
2 x (10 – 70)
Stranded (mm
2
)
1 x (16 – 120)
2 x (16 – 95)
1 x (16 – 95)
2 x (16 – 70)
1 x (16 – 120)
2 x (16 – 95)
1 x (16 – 120)
2 x (16 – 95)
Solid or Stranded (AWG) 10 – 250ACM 10 – 250ACM 8 – 250 MCM 8 – 250 MCM
Flat Conductor
(Number of Segments x Width x Thickness)
2 x (6 x 16 x 0.8) 2 x (6 x 16 x 0.8) 2 x (6 x 16 x 0.8) 2 x (6 x 16 x 0.8)
Main Cable Connection Screw/Bolt
Tightening torque
Nm
M10
14
M10
14
M10
14
M10
14
Control Circuit Cable Cross-Sections
Solid (mm
2
)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
1 x (0.75 – 4)
Flexible with ferrule (mm
2
)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
Solid or Stranded (AWG) 18 – 14 18 – 14 18 – 14 18 – 14
Control Circuit Cable Connection Screw/Bolt
Tightening torque
Nm
M3.5
1.2
M3.5
1.2
M3.5
1.2
M3.5
1.2