Eaton XT-40 User Manual Page 164

  • Download
  • Add to my manuals
  • Print
  • Page
    / 176
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 163
162 Technical details PG03407001U – June 2006
Technical details
What feeder circuit devices do you need for Type 2?
Achieving Type 2 is straightforward when using the following selection tables. Follow these steps to ensure that Type 2
coordination is in place:
Step 1: Determine the motor kW (single or three phase) or full load motor current from the motor nameplate.
Step 2: Verify the motor full load amps are less than or equal to the operational current (I
e
) listed next to the kW in the table.
Step 3: Manual Motor Controllers (MMC): Read across the tables horizontally for catalogue numbers of the Manual Motor
Protector (MMP) and contactor (customer assembly) or pre-assembled Manual Motor
Controller.
Note:
For certain kW ratings at 480V and 600V, a current limiter must be used to achieve the maximum Type 2 rating (shown in the following tables). Customers can either order the
MMP and Current Limit Contactors or an assembled MMC and current limiter.
Circuit breaker combination controllers: Read across the tables horizontally to determine the catalogue numbers of the
circuit breaker to be used in conjunction with the contactor and overload relay listed (customer assembly) or the pre-assem-
bled motor starter.
Fused combination controllers: Read across the tables horizontally to determine what amperage size fuse (customer to
specify brand) and the catalogue numbers of the contactor and overload relay or the pre-assembled motor starter.
Manual Motor Controller Combinations
1)
Values in parentheses ( ) are for Type 1 Coordination.
2)
Underscore (_) indicates coil suffix required.
400/415V Type 2 Coordination, MMC
P
(kW)
I
e
(A)
I
q
(kA)
MMP
Eaton
list number
Contactor
Eaton
list number
2)
MMC
Eaton
list number
2)
0.06 0.21
50.00 (150.00)
1)
XTPRP25BC1 XTCE007B10_ XTSCP25BB_
0.09 0.31
50.00 (150.00)
1)
XTPRP40BC1 XTCE007B10_ XTSCP40BB_
0.12 0.41
50.00 (150.00)
1)
XTPRP63BC1 XTCE007B10_ XTSCP63BB_
0.18 0.60
50.00 (150.00)
1)
XTPRP63BC1 XTCE007B10_ XTSCP63BB_
0.25 0.80
50.00 (150.00)
1)
XTPR001BC1 XTCE007B10_ XTSC001BB_
0.37 1.10
50.00 (150.00)
1)
XTPR1P6BC1 XTCE007B10_ XTSC1P6BB_
0.55 1.50
50.00 (150.00)
1)
XTPR1P6BC1 XTCE007B10_ XTSC1P6BB_
0.75 1.90
50.00 (150.00)
1)
XTPR2P5BC1 XTCE007B10_ XTSC2P5BB_
1.10 2.60
50.00 (150.00)
1)
XTPR004BC1 XTCE007B10_ XTSC004BB_
1.50 3.60
50.00 (150.00)
1)
XTPR004BC1 XTCE007B10_ XTSC004BB_
2.20 5.00
50.00 (150.00)
1)
XTPR6P3BC1 XTCE007B10_ XTSC6P3BB_
3.00 6.60
50.00 (150.00)
1)
XTPR010BC1 XTCE018C10_ XTSC010BC_
4.00 8.50
50.00 (150.00)
1)
XTPR010BC1 XTCE018C10_ XTSC010BC_
5.50 11.30 50.00 XTPR012BC1 XTCE018C10_ XTSC012BC_
7.50 16.00 50.00 XTPR016BC1 XTCE018C10_ XTSC016BC_
11.00 21.70 50.00 XTPR025BC1 XTCE025C10_ XTSC025BC_
15.00 29.30 50.00 XTPR032BC1 XTCE032C10_ XTSC032BC_
5.50 11.30 50.00 XTPR016DC1 XTCE018C10_ XTSC016DC_
7.50 16.00 50.00 XTPR016DC1 XTCE018C10_ XTSC016DC_
11.00 21.70 50.00 XTPR025DC1 XTCE025C10_ XTSC025DC_
15.00 29.30 50.00 XTPR032DC1 XTCE032C10_ XTSC032DC_
18.50 36.00 50.00 XTPR040DC1 XTCE040D00_ XTSC040DD_
22.00 41.00 50.00 XTPR050DC1 XTCE050D00_ XTSC050DD_
30.00 55.00 50.00 XTPR058DC1 XTCE065D00_ XTSC058DD_
34.00 63.00 50.00 XTPR063DC1 XTCE065D00_ XTSC063DD_
Page view 163
1 2 ... 159 160 161 162 163 164 165 166 167 168 169 ... 175 176

Comments to this Manuals

No comments