134 Technical details PG03407001U – June 2006
Technical details
1)
Rated operational current: Making and breaking conditions to DC-13, L/R constant as stated.
Standard, Overload Relays, Technical Data and Standards
Description XTOB…BC1, XTOB…CC1 XTOB…DC1
Auxiliary and Control Circuit Connections
Impulse Withstand Voltage (U
imp
) VAC 6000 6000
Overvoltage Category/Pollution Degree III/3 III/3
Terminal Capacity
Solid, mm
2
Flexible with ferrule, mm
2
Solid or stranded, AWG
2 x (0.75 – 4)
2 x (0.75 – 2.5)
2 x (18 – 12)
2 x (0.75 – 4)
2 x (0.75 – 2.5)
2 x (18 – 12)
Terminal Screw
Tightening Torque
Nm
M3.5
0.8 – 1.3
M3.5
0.8 – 1.3
Tools
Pozidrive screwdriver
Standard screwdriver
Size 2
1 x 6
Size 2
1 x 6
Auxiliary Circuit Rated Insulation Voltage (U
i
) VAC 500 500
Rated Operational Voltage (U
e
) VAC 500 500
Safe Isolation to VDE 0106 Part 101 and Part 101/A1
Between the auxiliary contacts (VAC) 240 240
Conventional Thermal Current, I
th
66
Rated Operational Current —
AC-15
NO Contact
120V
240V
415V
500V
1.5
1.5
0.5
0.5
1.5
1.5
0.5
0.5
NC Contact
120V
240V
415V
500V
1.5
1.5
0.9
0.8
1.5
1.5
0.9
0.8
Rated Operational Current —
DC-13 L/R <
15 mS
1)
24V
60V
110V
220V
0.9
0.75
0.4
0.2
0.9
0.75
0.4
0.2
Short Circuit Rating without Welding