16−2
EATON Powerware 9315 Parallel Capacity/Redundant System
164201150 Rev. E www.powerware.com
16.3 SBM Output
Output Voltage
(UPM Dependent)
480 VAC nominal (60 Hz only)
600 VAC nominal (60 Hz only)
400 VAC nominal (50/60 Hz)
Output Frequency Range "3 Hz of nominal (50 Hz or 60 Hz)
Output Current Model 600: 600 Amps
Model 800: 800 Amps
Model 1000: 1000 Amps
Model 1200: 1200 Amps
Model 1600: 1600 Amps
Model 2000: 2000 Amps
Overload Capability Alarm only. Trip Delay customer adjustable in
accordance with breaker manufacturer
specifications.
16.4 Environmental Specifications
Operating Temperature 0 to 40°C without derating. The recommended
operating temperature is 25°C.
Operating Altitude Maximum 1500m (5000 ft) at 40_C without
derating
Storage Temperature −20 to +70°C (prolonged storage above 40°C
will cause rapid battery self-discharge)
Relative Humidity (operating and
storage)
95% maximum noncondensing
Acoustical Noise N/A
EMI Suppression Meets FCC Regulation 47, Part 15, Subpart J, for
class A devices
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801−2 specifications. Withstands up
to 25 kV without damage and with no disturbance
or adverse effect to the critical load.