80 30-200 kW P-164000249
User's and Installation Guide Revision 2
Ambient service temperature range, (UPS) From +5 °C to +40 °C*
No output power derating required.
Relative humidity range 5 to 95 %, no condensation allowed
Maximum service altitude 1000 m (3300 ft) above sea level
Maximum 2000 m (6600 ft) with 1 % derating
per each additional 100 m.
Table 8-5: UPS environmental specifications
*Maximum recommended operating and storage temperature with VRLA batteries is +25 °C.