P-164000249 30-200 kW 31
Revision 2 User's and Installation Guide
The bypass feed into this equipment uses four wires. The rectifier feed into this equipment uses
three or four wires. The phases must be symmetrical about ground (from a Wye source) for
proper equipment operation.
If the load requires a neutral, a bypass source neutral must be provided. If the load does not
require a neutral and there is no neutral conductor connected at the bypass input, a neutral must
be installed to source star point.
A readily accessible disconnect device must be incorporated in all fixed input wiring.
UPS
rating
Rectifier input Bypass input
UPS
output
(380/400/
415V)
PE Battery
Fuse Cable Fuse Cable Cable Cable Fuse Cable
50 kW 3x 100
A
4x 35
mm²
3x 100
A
4x 35
mm²
4x 35
mm²
35 mm² 200 A 2x 70
mm²
50 kW
Maximum
- 4x 50
mm²
- 4x 50
mm²
4x 50
mm²
35 mm² - 2x 95
mm²
100 kW 3x 200
A
4x 70
mm²
3x 200
A
4x 70
mm²
4x 70
mm²
35 mm² 400 A 2x 150
mm²
150 kW 3x 315
A
4x 150
mm²
3x 315
A
4x 150
mm²
4x 150
mm²
95 mm² 500 A 4x 150
mm²
200 kW 3x 400
A
4x 240
mm²
3x 400
A
4x 240
mm²
4x 240
mm²
120
mm²
630 A 4x 240
mm²
Table 3-6: Minimum recommended multi-core cable and fuse sizes
Rated
power
Rated
voltage
Rectifier
input
Rated
current
Rectifier
input
Max.
current
UPS
Output/
Bypass
Rated
current
UPS
Output/
Bypass
Max.
current
Battery
Rated
current
Battery
Max.
current
380 V 48 57 46 55 73 95
400 V 46 54 44 52 73 95
30 kW
415 V 44 52 42 50 73 95
380 V 64 76 62 73 97 126
400 V 61 72 59 70 97 126
40 kW
415 V 58 69 56 66 97 126
50 kW 380 V 80 95 77 91 121 158