Instruction Manual IM01005019E - Rev.5
Effective November 2013
Eaton www.eaton.com 7
Eaton SPD Series
Surge Protective Device for Integrated Units
3.0 Operating Features
3.1 General
The Eaton SPD Series comes in three feature packages: Basic,
Standard, and Standard with Surge Counter. The operating spe-
cifics of each feature package are described below.
The Eaton SPD Series requires no operator involvement, other
than to monitor the display panel to determine status of the
SPD.
After system power is applied, the SPD automatically begins
protecting downstream electrical equipment from voltage tran-
sients.
Some SPD units have a Form C relay contact that allows for the
remote indication of SPD status. Form C contact wires are con-
nected via a three terminal connector. See Figure 13.
3.2 Displays and Indicators
All Eaton SPD Series units (Basic, Standard, and Standard With
Surge Counter) use a display panel to indicate system status.
The display panel is slightly different for each feature package.
Each display has both green and red light emitting diodes
(LEDs) to indicate the status of the protection on each phase.
Green indicates the phase is fully protected. Red indicates a
loss of protection. Wye, Split Phase and High-Leg Delta units
have an additional set of green/red LEDs to indicate status of
Neutral/Ground protection.
When the LEDs turn red, an audible alarm will also sound on
units equipped with an audible alarm.
Specific operating conditions displayed for each Eaton SPD
Series Feature Package are described below.
3.2.1 Basic Feature Package
The Eaton SPD Basic Feature Package display is shown in
Figure 18.
The Basic Feature Package has the following features:
Green LEDs: Illumination indicates the phase is fully pro-
tected, and operating normally, with all protection active and
available. Green LEDs also indicate Neutral to Ground protec-
tion on units with a Neutral wire. Green LEDs do not indicate
on/off status of power.
Red LEDs: Illumination indicates a loss of protection, and
that one or more protective devices are now inactive and
unavailable for that Phase. Red LEDs also indicate Neutral to
Ground protection on units with a Neutral wire. Red LEDs do
not indicate on/off status of power.
3.2.2 Standard Feature Package
The Eaton SPD Series Standard Feature Package display is
shown in Figure 19.
The Standard Feature Package has the following features:
All features of the Basic Feature Package.
One Form C relay contact rated at 150Vac or 125Vdc @1A.
Normal operating conditions. N.O. = OPEN. N.C =
CLOSED.
Loss of protection on any phase or loss of power. N.O. =
CLOSED. N.C. = OPEN.
Audible alarm with Reset push button.
EMI/RFI filtering.
3.2.3 Standard With Surge Counter Feature Package
The Eaton SPD Series Standard With Surge Counter Feature
Package display is shown in Figure 20.
The Standard With Surge Counter Feature Package has the fol-
lowing features:
All features of the Standard Feature Package.
LCD screen that displays surge count.
Reset button to RESET the surge counter to zero.
Figure 18. Basic Feature Package Display
Figure 19. Standard Feature Package Display
Figure 20. Standard With Surge Counter Feature Package
Display