Effective November 2013
8 Eaton www.eaton.com
Eaton SPD Series
Surge Protective Device for Integrated Units
Instruction Manual IM01005019E - Rev. 5
3.3 Remote Display Panel (RDP) Option
The Eaton Series SPD displays may be monitored on a remote
display panel (RDP). This is indicated by the catalog style with a
'B' suffix (such as SPD250480D2B).
A separately purchased RDP cable is required to connect the
SPD unit to the display.
Table 2 lists these cables and their part numbers.
Table 2. RDP Cable Options
Description
Catalog No.
4 ft. Cable for RDP
8 ft. Cable for RDP
12 ft. Cable for RDP
SPDRDCAB04
SPDRDCAB08
SPDRDCAB12
3.4 IEC Approved Models
Eatons One-Port low-voltage Surge Protective Device Wye
Models SPD120480Y2C, SPD160480Y2C, SPD200480Y2C
and Delta Models SPD120480D2C, SPD160480D2C,
SPD200480D2C meet the requirements of IEC 61643-11 / EN
61643-11, Part 11: Test Class II, and are intended to be installed
in indoor applications with a degree of protection rated IP 00.
The SPD Delta and Wye Models are intended for use with a 3
Phase TN-S System with PE and Neutral Distribution, 5 conduc-
tor with a minimum 10 AWG or 6 mm
2
. The Delta Models are
also intended for use with a 3 Phase TN-C System with PEN
Distribution, 4 conductor with a minimum 10 AWG or 6mm
2
.
Screws used for connection to ground shall be #10-32 x 3/8”
and shall not be zinc or aluminum. This product is not service-
able and contains no replaceable parts.
Additional product information and ratings for IEC Applications:
The SPD contains internal disconnects with a short circuit
current rating I
SCCR
of 200kA.
Residual Current IPE for this product is 5 mA.
Operating temperature is Normal -5°C to 40°C (23°F to
104°F.
Humidity range is 5% through 95% non-condensing.
The SPD may be mounted directly to earthed conductive
surface, installed as per this manual.
Temporary overvoltage rating UT = 402.6 V.
Withstand or safe failure mode, for tT = 120 minutes,
UT = 526 V.
Modes of protection as marked on a Wye SPD = L - L, L - N,
L - G(PE), N - G(PE).
Modes of protection as marked on a Delta SPD = L - L,
L - G(PE).
3.2.4 SPD Display Rotation
The SPD display can be rotated on the SPD enclosure, up to 360
degrees. This allows you to position the display for the best vis-
ibility regardless of the position in which the SPD is installed.
Rotations are at 90, 180, and 270 degrees.
For a typical horizontal mounting see Figure 21. For a typical ver-
tical mounting see Figure 22.
Reposition the SPD display as follows:
1. Remove power from the unit.
2. Remove and discard the perforated overlay material at the
two opposite corners of the display.
3. Remove the two phillips head screws that hold the display.
4. Rotate the display to the desired position. Be careful not to
overstress the display ribbon cable.
5. Place the display back onto the SPD enclosure. Again, be
careful not to overstress or crimp the ribbon cable.
6. Replace the two phillips head screws. Tighten screws to
1.35 Nm (12 in-lbs).
7. Restore power to the unit.
Figure 21. Typical Horizontal Display Mounting
Figure 22. Typical Vertical Display Mounting