ADDITIONAL UPS FEATURES
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
44
Table 6. Voltage Threshold O ptions (continued)
PW5130G3000-XL2U Function Factory Setting Other Available Settings
High threshold for transfer to battery
263 Vac
Low threshold for transfer to battery
160 Vac
Fader activation threshold
229 Vac
Booster activation threshold
177 Vac
Maximum input-voltage range
Disabled Enabled
2
2
Low threshold for transfer to battery is 150V.
Table 7. UPS Sensitivity Options
Function
Factory Setting Other Available Settings
UPS-sensitivity level
Normal High or low
Table 8. UPS On/Off Options
Function
Factory Setting Other Available Settings
Automatic start
Enabled Disabled
Cold start
Enabled Disabled
Forced shutdown
Enabled Disabled
Energy-savings mode
Disabled Enabled
UPS ON/OFF controlled by software
Enabled Disabled
Battery level before restart
0% 0–100%
Table 9. Battery Options
Function
Factory Setting Other Available Settings
Battery-test intervals
Weekly No test / daily test / monthly test
Low-battery warning
20% 0–100%
Battery protection against deep discharge
Enabled Disabled
Audio alarm
Enabled Disabled
Additional battery module
Automatic detection of number of
battery modules
For specific batteries, 25–81 Ah