Eaton Powerware 5130 Rack/Tower UPS 1250-3000 VA User's Guide Page 49

  • Download
  • Add to my manuals
  • Print
  • Page
    / 74
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 48
ADDITIONAL UPS FEATURES
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
43
Customizing the UPS with the UPS Configuration Tool
To customize the UPS settings:
1. Download the UPS Configuration tool from www.powerware.com.
2. Follow the on-screen instructions for the Powerware 5130.
It is possible to modify the settings listed below (detailed
comments are available in the UPS Configuration tool).
Table 5. Main Output Options
Function Factory Setting Other Available Settings
Low-Voltage Models. Output voltage on
battery power
120 Vac 100/120/127 Vac
High-Voltage Models. Output voltage on
battery power
230 Vac 200/208/220/240 Vac
PW5130G3000-XL2U Models. Output
voltage on battery power
208V
All Models. Overload alarm threshold
105% 30/50/70%
Table 6. Voltage Threshold O ptions
Low-Voltage Model Function Factory Setting Other Available Settings
High threshold for transfer to battery
151 Vac ±3% 141–153 Vac
Low threshold for transfer to battery
89 Vac ±3% 89–94 Vac
Fader activation threshold
132 Vac ±3% 127–138 Vac
Booster activation threshold
102 Vac ±3% 92–108 Vac
Maximum input-voltage range
Disabled Enabled
1
High-Voltage Model Function Factory Setting Other Available Settings
High threshold for transfer to battery
294 Vac 271–294 Vac
Low threshold for transfer to battery
160 Vac 160–180 Vac
Fader activation threshold
265 Vac 244–265 Vac
Booster activation threshold
184 Vac 184–207 Vac
Maximum input-voltage range
Disabled Enabled
2
1
Low threshold for transfer to battery is 70V.
2
Low threshold for transfer to battery is 150V.
Page view 48