Eaton 6000 VA User's Guide Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
Page 8
9130 UPS-EN
2. Installation
2.6 Connecting the EBM(s)
To install the optional EBM(s) for a UPS:
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal
and will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and
firmly.
1. Plug the EBM cable(s) into the battery connector(s) as shown in figure 7. Up to four EBMs may be
connected to the UPS.
2. Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for
each cable.
3. When using external battery cabinets, the number of EBMs should be set throw the LCD panel in the
"Battery settings" section, see "Configuring battery settings" on page 20.
4. Continue to "Installation requirements" on page 8.
Figure 7. Connecting the EBMs.
2.7 Installation requirements
Required protective devices and cable cross-sections
1. Recommended upstream protection (see figure 8)
Table 1. Upstream circuit breaker rating
UPS power rating Upstream circuit breaker
5000 VA / 6000 VA D curve – 40 A
G N L
N
L
Figure 8. Upstream protection.
2 poles circuit breaker
To UPS input source
and/or Bypass source.
Page view 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 35 36

Comments to this Manuals

No comments