Eaton 6000 VA User's Guide Page 24

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 23
Page 24
9130 UPS-EN
5. Communication
The table 10 shows the options for the relay output contacts.
Table 10. Relay Output Configuration Options
Relay Signal Description
UPS ok Activated when the UPS is feeding the load on inverter or on bypass and no
alarms are active
On Bypass Activated when the UPS is NOT on bypass operation
On Battery Activated when the UPS operates on battery and the "On Battery Notice
Delay" time has expired
Battery Low Activated with the "Battery Low" alarm according to the "Battery Low Alarm"
setting
Ext. Charger On Controls an optional external battery charger on and off
The figure 25 shows the connection of the relay output contacts.
1 2 3
Figure 25. Standard Relay Port Connections.
The figure 26 shows an example where a lamp is connected on the relay output contacts.
1 3
G
2 3
G
Relay signal L1 L2
True
Not true
G : external power supply
Figure 26. Example of Standard Relay Port Connections with lamp.
Programmable Signal Inputs
The UPS incorporates four programmable signal inputs: one RS 232 input, two connectivity card inputs,
and one RPO terminal input. See figure 21 on page 21 for the locations of the ports. Configure the
inputs with the "Signal Inputs" setting in "User Settings" on page 15.
The table 11 shows the programmable settings for the signal inputs. Table 12 shows the operation logic
for the signal inputs.
Table 11. Programmable Signal Inputs
Signal Description
Not Used The input operates only as a serial input (RxD) or has no function.
Force Bypass If active, the UPS is forced to static bypass operation regardless of the bypass
status.
Remote
Shutdown
If active, the UPS output turns off after a user-defined remote shutdown delay.
The batteries continue charging. Inactive input does not abort the shutdown
countdown and does not cause the UPS to start up automatically.
Delayed
Shutdown
(and restart)
If active, the UPS output turns off after a user-defined delayed shutdown delay.
The batteries continue charging. Inactive input does not abort the shutdown
countdown but will cause the UPS to start up automatically if the input voltage
exists.
On Generator If active, synchronization is disabled and the UPS transfers to bypass.
Building Alarm 1 If active, the UPS generates the "Building Alarm 1" alarm.
Common
CommonCommon
Normally closed
Normally open
Normally
open
Normally
closed
Page view 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 35 36

Comments to this Manuals

No comments