Eaton RF System 2.30Manual
10 Eaton RF-System - Help© 2013 Eaton Electrical GroupWhat was new for 1.60?Room-Manager V38a is supported, new and extended features at rooms, logica
100 Eaton RF-System - Help© 2013 Eaton Electrical GroupPlease note that you only use outputs for the presence simulation that are not already used as
101Eaton RF-System© 2013 Eaton Electrical GroupThe defined action is only executed if the logic operation between the 2 starting variables switchesfro
102 Eaton RF-System - Help© 2013 Eaton Electrical GroupBy „add action“ and „remove action“ you can set which things the scene should do or removethem.
103Eaton RF-System© 2013 Eaton Electrical Group-) 3 zones (zone 1, zone 2, zone1+2)General information:All sensors used for the safety function need t
104 Eaton RF-System - Help© 2013 Eaton Electrical Groupto be created as an output at the Room Manager.Also refer to chapter Room Manager with Safety F
105Eaton RF-System© 2013 Eaton Electrical GroupField 4:If this option has been activated, the Room Manager will give an acoustic alarm once in a minut
106 Eaton RF-System - Help© 2013 Eaton Electrical GroupHere you can define a name for the different Safety Inputs. There is a max. of 10 Safety Inputs
107Eaton RF-System© 2013 Eaton Electrical GroupThe window is set up as follows: Field 1:Here you can define the names of the different smoke detector
108 Eaton RF-System - Help© 2013 Eaton Electrical GroupAlso refer to chapter Room Manager with Safety Function – Overview General Information on the R
109Eaton RF-System© 2013 Eaton Electrical GroupAlso refer to chapter Room Manager with Energy Function – Input with Energy measuring Sensor Also refer
11Eaton RF-System© 2013 Eaton Electrical GroupNow that you have scanned your system, you can start with its configuration.To change the position of a
110 Eaton RF-System - Help© 2013 Eaton Electrical Groupcounter is the same as the Alltime value displayed at the Room Manager. New since RM V38:Gen
111Eaton RF-System© 2013 Eaton Electrical GroupAlso refer to chapter General Information on the Room Manager with Energy FunctionRoom Manager with Ene
112 Eaton RF-System - Help© 2013 Eaton Electrical GroupShow text or chart page on the Room-Manager – It is possible to display or to hide the text or
113Eaton RF-System© 2013 Eaton Electrical GroupThis is what the setting window for the energy input assigned to a tariff energy channel of the xCMEP d
114 Eaton RF-System - Help© 2013 Eaton Electrical GroupGeneral:Name: Here you can enter the name of the energy input (max. 13 characters)Connected dev
115Eaton RF-System© 2013 Eaton Electrical GroupTariff per measuring unit: Enter the tariff per measuring unit hereCO2 per kWh: Here you can enter the
116 Eaton RF-System - Help© 2013 Eaton Electrical GroupSetting possibilities:Name: Here you can enter the name of the page (max. 13 characters)Display
117Eaton RF-System© 2013 Eaton Electrical GroupRoom Manager with Energy Function – Overview Page:At the energy overview page you can display again 3 l
118 Eaton RF-System - Help© 2013 Eaton Electrical GroupYou can define up to 3 predefined SMS texts. It can be selected for sending in the ‘alarms” pag
119Eaton RF-System© 2013 Eaton Electrical GroupHere you can define how the Room-Manager will react on 3 different events.Possible events are: Marker t
12 Eaton RF-System - Help© 2013 Eaton Electrical GroupQuitQuits the configuration software of the xComfort componentsThe Command New (File Menu)Use th
120 Eaton RF-System - Help© 2013 Eaton Electrical GroupRoom-Manager with Bluetooth-function - Calls:The configuration window looks like:Start action b
121Eaton RF-System© 2013 Eaton Electrical GroupThe following settings can be done:‘Enable control and request via SMS’ – If this option is deactivated
122 Eaton RF-System - Help© 2013 Eaton Electrical Group‘Set/interrogate marker by SMS’ – If this option is activated also state of markers can be requ
123Eaton RF-System© 2013 Eaton Electrical Group<State>:Syntax of RM to user:
124 Eaton RF-System - Help© 2013 Eaton Electrical GroupBasic information for Room-Manager Bluetooth:The primary function for the Room-Manager Bluetoot
125Eaton RF-System© 2013 Eaton Electrical GroupManager has been connected to.7. Now go back to MRF and right click on your Room Manager and select „Lo
126 Eaton RF-System - Help© 2013 Eaton Electrical GroupAs you can see in the picture for every day you can set 3 different time spans with differentop
127Eaton RF-System© 2013 Eaton Electrical GroupSetting of Delay time for Channel A:The Switch-Off delay time for channel A can be set to the following
128 Eaton RF-System - Help© 2013 Eaton Electrical GroupIf the setting is 1 impulse the motion detector reacts immediately on movement. If the setting
129Eaton RF-System© 2013 Eaton Electrical GroupYou can set if channel A and/or channel B should be send cyclically and how fast a RF-commandis sent.Yo
13Eaton RF-System© 2013 Eaton Electrical GroupDetailed Info of all Devices...Here you will find a list of detailed data on scanned Devices , among oth
130 Eaton RF-System - Help© 2013 Eaton Electrical Group2. Download file setup_ci_update.zip (you will find a link athttp://www.moeller.at/de/service/d
131Eaton RF-System© 2013 Eaton Electrical Groupswitching of an actuator. FAQsWhy are there two different interfaces, CRSZ-00/01 and CKOZ-00/03?The RS
132 Eaton RF-System - Help© 2013 Eaton Electrical GroupIn this mode a switching command is sent. The time at which the switching command is sentdepend
133Eaton RF-System© 2013 Eaton Electrical GroupThe measured and converted value is sent by menu item “Send measured value”.You can select how many tim
134 Eaton RF-System - Help© 2013 Eaton Electrical GroupIn this case the direct measured value (0-100%) is sent to a dimming actuator or analog actuato
135Eaton RF-System© 2013 Eaton Electrical Group: long press on the button, top: long press on the button, bottom: short press on the button, bottom12-
136 Eaton RF-System - Help© 2013 Eaton Electrical GroupThe number of the pre-selection button (1 to 6) is shown to the left, whilst the level (1 and 2
137Eaton RF-System© 2013 Eaton Electrical GroupRouting actuator:The routing actuator is a device which is incorporated in the system and which can be
138 Eaton RF-System - Help© 2013 Eaton Electrical Grouplogic function.Activating the option ‚Release Logic X‘ will enable the logic for configuration.
139Eaton RF-System© 2013 Eaton Electrical GroupImpulse input:The impulse input counts the impulses at its 2 separate S0 interfaces and forwards the re
14 Eaton RF-System - Help© 2013 Eaton Electrical GroupThe Commands 1, 2, 3, 4 (File Menu)Use the numbers and file names listed at the end of the File
140 Eaton RF-System - Help© 2013 Eaton Electrical GroupThe name of each output can be freely defined or selected from a predefined list of names. Both
141Eaton RF-System© 2013 Eaton Electrical GroupRemote Control with Display - Timer:A maximum of 3 timers can be linked with each output. Under "
142 Eaton RF-System - Help© 2013 Eaton Electrical GroupThe following settings can be done: -) automatic changing of the clocks from summer time to win
143Eaton RF-System© 2013 Eaton Electrical Group8. You will see this window appear:9. Select the new software you wish to load (*.fb)10. Select the COM
144 Eaton RF-System - Help© 2013 Eaton Electrical GroupEnergy:The channel for energy is always active and the transmission of values cannot be deactiv
145Eaton RF-System© 2013 Eaton Electrical GroupDefined by what device is assigned to it in the MRF program it can be used in 3 different modes:1. Oper
146 Eaton RF-System - Help© 2013 Eaton Electrical GroupIn this mode the operation mode is controlled by the Room controller (via the switch). It can b
147Eaton RF-System© 2013 Eaton Electrical Group3. Operation with Room-Manager:The heating actuator is assigned as the heating request for a room of th
148 Eaton RF-System - Help© 2013 Eaton Electrical GroupThe control of the operation mode is done by the Room-Manager (timer program or manual). It can
149Eaton RF-System© 2013 Eaton Electrical Groupconnected.If a sensor is occupied the device will send the command <SWITCHED ON>, if its not occu
15Eaton RF-System© 2013 Eaton Electrical GroupConnecting two xComfort devices is possible by left-clicking and holding a device icon. Now selectthe re
150 Eaton RF-System - Help© 2013 Eaton Electrical GroupOverview MEP deviceThe MEP device is connected to an Eaton Smart Meter and transfers different
151Eaton RF-System© 2013 Eaton Electrical GroupMEP device - Total Energy:On this page you can configure the total energy channel of the MEP device and
152 Eaton RF-System - Help© 2013 Eaton Electrical GroupRate 1 Energy value: Transmission of the rate 1 Energy value activated/deactivated and definiti
153Eaton RF-System© 2013 Eaton Electrical Group Configuration and cyclical transmission (every hour) of the status of each rate output. (only if thera
154 Eaton RF-System - Help© 2013 Eaton Electrical Groupsee Overview MEP deviceMEP device - General:On this page general information is displayed and t
155Eaton RF-System© 2013 Eaton Electrical GroupAfter the successful configuration and the activation of the option “The MEP device has beenconfigured
156 Eaton RF-System - Help© 2013 Eaton Electrical Group Assigned device:In the stand alone operation there is no assigned device. Furthermorethe funct
157Eaton RF-System© 2013 Eaton Electrical Groupa time) of the detection.Further the time for the heating break can be defined. After this breakthe the
158 Eaton RF-System - Help© 2013 Eaton Electrical GroupAssigned device:The name of the connected intelligent device will be displayed here You shoul
159Eaton RF-System© 2013 Eaton Electrical Grouptemperature. This also works if the operation mode of the intelligent deviceis switched to OFF.Open win
16 Eaton RF-System - Help© 2013 Eaton Electrical Group”Display reception quality of this device” -> shows the reception quality lines from this dev
160 Eaton RF-System - Help© 2013 Eaton Electrical GroupEthernet Routing activated, used as Ethernet-Communication nodeTo change the settings of the Et
161Eaton RF-System© 2013 Eaton Electrical GroupAfter all connections have been drawn a datapoint list needs to be created. New is the possibility toei
162 Eaton RF-System - Help© 2013 Eaton Electrical GroupHelp Network testHelp Network settingsNetwork test:The network test can be used to check the LA
163Eaton RF-System© 2013 Eaton Electrical GroupIP-settings:IPv4:Address - IPv4 Address of the ECI in the format "x.y.y.y" (x: 1-255, y: 0-25
164 Eaton RF-System - Help© 2013 Eaton Electrical GroupPlease make sure that every ECI in the project has a unique IP-address or it will not workcorr
165Eaton RF-System© 2013 Eaton Electrical GroupIn this configuration the Multi-Heating actuator works in the operation type Heating only therefor were
166 Eaton RF-System - Help© 2013 Eaton Electrical GroupWe recommend plugging the jumpers on the Multi-Heating actuator for each channel to „Heatingonl
167Eaton RF-System© 2013 Eaton Electrical GroupWe recommend plugging the jumpers on the Multi-Heating actuator for each channel to „Heatingonly“, “Coo
168 Eaton RF-System - Help© 2013 Eaton Electrical GroupSave as file: The possibility to save the list as a file in the TXT- or the extended DPL-format
169Eaton RF-System© 2013 Eaton Electrical GroupApple iPhone or iPad with iOS App (App Store)Android Smartphone or Tablet with Android App (Google Play
17Eaton RF-System© 2013 Eaton Electrical GroupLoad passwordAll devices forming part of the project which do not yet have the current password are load
170 Eaton RF-System - Help© 2013 Eaton Electrical GroupBasic Mode:Is currently not supported by the smart home controller softwareSwitching actuator 1
171Eaton RF-System© 2013 Eaton Electrical Groupdefinable minimum consuming power.Each function (actuator, Binary input, Energy measurement) has its ow
172 Eaton RF-System - Help© 2013 Eaton Electrical GroupActuator-Function:Configuration window actuator – function:After drawing the desired connection
173Eaton RF-System© 2013 Eaton Electrical GroupIn the Tab ‚Switching actuator‘ all configuration possibilities for the actuator function can be set.Th
174 Eaton RF-System - Help© 2013 Eaton Electrical Groupsituated next to them. As you will see later, different functions can now be assigned to thesec
175Eaton RF-System© 2013 Eaton Electrical Groupoutput action for Release Lock can be defined (ON, OFF, old value)No Function, occupies 1 command butto
176 Eaton RF-System - Help© 2013 Eaton Electrical GroupOff with Advance Warning free selectable for and Push-button/Key Mode free selectable for a
177Eaton RF-System© 2013 Eaton Electrical Groupalso see:Switching actuator 10A/16A - GeneralSwitching actuator 10A/16A – Actuator functionSwitching ac
178 Eaton RF-System - Help© 2013 Eaton Electrical Groupstatus message of the actuator will also be sent if the power value changes according to thesen
179Eaton RF-System© 2013 Eaton Electrical GroupSwitching actuator 10A/16A – Extended Status messageExtended Status message:General Information:The ext
18 Eaton RF-System - Help© 2013 Eaton Electrical GroupHere you can define the serial interface port (COM Port), where the Gateway is connected.The qua
180 Eaton RF-System - Help© 2013 Eaton Electrical Group
181Eaton RF-System© 2013 Eaton Electrical GroupStructure of the new extended Status-message:The extended Status message includes the following informa
182 Eaton RF-System - Help© 2013 Eaton Electrical Groupsending of the new status message of each new actuator will be delayed differently in order toh
183Eaton RF-System© 2013 Eaton Electrical Group3. The standard function ON/OFF at and is pre-set and will not be modified. Instead, we click the c
184 Eaton RF-System - Help© 2013 Eaton Electrical Group4. Now we select the desired function (e.g.: On / switch-on delay)
185Eaton RF-System© 2013 Eaton Electrical Group5. As you will see, the command button now displays the name of our function and you canselect the co
186 Eaton RF-System - Help© 2013 Eaton Electrical Group6. Then we select the command button for (long push at the bottom of the key).
187Eaton RF-System© 2013 Eaton Electrical Group7. And assign the function Blinking to it.
188 Eaton RF-System - Help© 2013 Eaton Electrical Group8. Again select the control time (1 second) and the interval time (10 seconds).An interval time
189Eaton RF-System© 2013 Eaton Electrical Group9. Now that all functions have been configured, let us select the behaviour in case of powerrecovery (O
19Eaton RF-System© 2013 Eaton Electrical Group-> edit -> Calculate all connections newNew: Scan also reception quality with normal data.When dea
190 Eaton RF-System - Help© 2013 Eaton Electrical Group10. The switching actuator configuration is completed and we confirm the configuration bypressi
191Eaton RF-System© 2013 Eaton Electrical GroupConfiguration Example of the Dimming ActuatorFor basic configuration, such as selecting the functions,
192 Eaton RF-System - Help© 2013 Eaton Electrical Group2. Then we change the dimming limits from the standard setting (20% to 100%) to 40% to 90%.
193Eaton RF-System© 2013 Eaton Electrical GroupThis modification means that the command sent by the hand-held transmitter starts dimming at40% brigh
194 Eaton RF-System - Help© 2013 Eaton Electrical GroupAfter a command, the actuator will now dim to the value of 80%.Configuration Example of the S
195Eaton RF-System© 2013 Eaton Electrical GroupConfiguration Example of the Room ControllerSending a switching command:A room controller is supposed t
196 Eaton RF-System - Help© 2013 Eaton Electrical GroupThen confirm with OK. Result: If the adjustment wheel is set to zero and the temperature is 25°
197Eaton RF-System© 2013 Eaton Electrical GroupIcons and their meaningDevice icons:Switching actuatorDimming actuatorShutter actuatorPush-button 1-fol
198 Eaton RF-System - Help© 2013 Eaton Electrical GroupTemperature input (Channel A)Temperature input (Channel B)Home Manager RFProtected access to th
199Eaton RF-System© 2013 Eaton Electrical GroupCommunication nodeEthernet CI with activated Ethernet Routing used asEthernet-Communication nodeRF Radi
Eaton RF-System - Help2© 2013 Eaton Electrical GroupContents...
20 Eaton RF-System - Help© 2013 Eaton Electrical GroupAfter a background grafic has been selected and the Open button has been activated, thebackgroun
200 Eaton RF-System - Help© 2013 Eaton Electrical GroupSwitched ONSwitched OFFFalling below the preset temperatureExceeding the preset temperatureHumi
201Eaton RF-System© 2013 Eaton Electrical GroupAs you can the command from 1-fold pushbutton to Switching actuator 3 is routed by Switchingactuator 1
202 Eaton RF-System - Help© 2013 Eaton Electrical GroupThe blue line goes from the sensor to the group master (Switching actuator 7). That actuatorack
203Eaton RF-System© 2013 Eaton Electrical GroupStep 1 – Select the desired actuators, the sensor and start the functionStep 2 – Select the sensor chan
204 Eaton RF-System - Help© 2013 Eaton Electrical GroupStep 4 - Configuration of device type dimming actuator
205Eaton RF-System© 2013 Eaton Electrical GroupStep 5 - Configuration of device type analogue actuator
206 Eaton RF-System - Help© 2013 Eaton Electrical GroupStep 6 - Configuration of device type shutter actuator
207Eaton RF-System© 2013 Eaton Electrical GroupThe configuration is now complete. Every selected actuator has been configured.Configure group basic se
208 Eaton RF-System - Help© 2013 Eaton Electrical Groupconnection to another device for example) it will also be locked for the whole group.For a grou
209Eaton RF-System© 2013 Eaton Electrical GroupGroup settings analogue actuator:
21Eaton RF-System© 2013 Eaton Electrical GroupEach project note can be positioned as desired in the project using drag & drop, and the heightand w
210 Eaton RF-System - Help© 2013 Eaton Electrical GroupGroup settings heating actuator:
211Eaton RF-System© 2013 Eaton Electrical GroupGroup settings binary input battery supplied:
212 Eaton RF-System - Help© 2013 Eaton Electrical GroupGroup settings binary input 230V:Group settings Motion detector:
213Eaton RF-System© 2013 Eaton Electrical GroupGroup settings Temperature input:
214 Eaton RF-System - Help© 2013 Eaton Electrical GroupGroup settings Room controller:Group settings Room controller with humidity:
215Eaton RF-System© 2013 Eaton Electrical GroupGroup settings Analogue input:Group settings Impulse input:
216 Eaton RF-System - Help© 2013 Eaton Electrical GroupGroup settings Energy measurement sensor:Group settings BOS/COS Interface:
217Eaton RF-System© 2013 Eaton Electrical GroupSettings that are locked and so can not be changed any more will not be displayed at all.After clicking
218 Eaton RF-System - Help© 2013 Eaton Electrical GroupDelete: Removes the device from the configuration and deletes it from the screenLoad default se
219Eaton RF-System© 2013 Eaton Electrical GroupFor battery-powered devices:Destination device – specifies the destination device and the next device f
22 Eaton RF-System - Help© 2013 Eaton Electrical GroupInsert group framesThis function offers the option of drawing frames with titles (max. 21 charac
220 Eaton RF-System - Help© 2013 Eaton Electrical GroupInsert copied devices:Inserts copied virtual devices from the clipboard to the selected positio
221Eaton RF-System© 2013 Eaton Electrical GroupThe device type of the scanned device and the actual name that can be changed (max. 21characters) will
222 Eaton RF-System - Help© 2013 Eaton Electrical GroupThe window is divided into the following areas:Connection from - sensor:Here, the previously-ch
223Eaton RF-System© 2013 Eaton Electrical GroupConnection to - Configure devices at the same time:By activating/deactivating this function, you can de
224 Eaton RF-System - Help© 2013 Eaton Electrical GroupPassword-selective scanning:Here you can decide if only those devices that satisfy the specific
225Eaton RF-System© 2013 Eaton Electrical GroupIf Yes, you will be shown the new password once again. If No, you will be shown the old passwordonce ag
226 Eaton RF-System - Help© 2013 Eaton Electrical GroupWhen you start a new project and click on “Scan”, this window also opens and you can define apa
227Eaton RF-System© 2013 Eaton Electrical Groupbutton will remain deactivated. If the selected software is valid the update process can be started by
228 Eaton RF-System - Help© 2013 Eaton Electrical Groupthey want to use the software update function. The USB-RF-Sticks need a specific driver duringt
229Eaton RF-System© 2013 Eaton Electrical GroupThe operating system simply informs you that the driver is not digitally signed. Please select theoptio
23Eaton RF-System© 2013 Eaton Electrical GroupInsert MRF projectThis function offers the option of inserting devices (incl. all settings) from an alre
230 Eaton RF-System - Help© 2013 Eaton Electrical GroupReconfirm your selection by clicking YES in the following window.Now the driver that has been p
Endnotes 2... (after index)231© 2013 Eaton Electrical Group
Back Cover
24 Eaton RF-System - Help© 2013 Eaton Electrical GroupInsert configuration template: All devices in the selected project will be inserted as virtua
25Eaton RF-System© 2013 Eaton Electrical GroupInsert virtual devicesWith this function, as many virtual devices of a selected type as desired can be i
26 Eaton RF-System - Help© 2013 Eaton Electrical GroupThis function can be repeated as often as desired. Insert devices by Barcode:With this new funct
27Eaton RF-System© 2013 Eaton Electrical GroupYou have the possibility to scan the Barcode by a normal USB-Barcode-Scanner or to enter theCode-numbers
28 Eaton RF-System - Help© 2013 Eaton Electrical GroupAfter the positive check of a Code this window will appear and inform about the details of the j
29Eaton RF-System© 2013 Eaton Electrical GroupRecalculate Resenders of oldStatus connectionsRecalculates the Resenders of old Status connectionsLoadMo
3Contents© 2013 Eaton Electrical Group...
30 Eaton RF-System - Help© 2013 Eaton Electrical GroupThere are some main supplied devices already scanned how you can see in the part list and therec
31Eaton RF-System© 2013 Eaton Electrical GroupData is being transmitted and if a new device is scanned it will be added to the part list.New main supp
32 Eaton RF-System - Help© 2013 Eaton Electrical GroupIf you have scanned all desired devices you can click on the „Quit“ button. When using thestanda
33Eaton RF-System© 2013 Eaton Electrical Groupdevices notice how good or bad they understand every message. Depending on the number ofdevices and thei
34 Eaton RF-System - Help© 2013 Eaton Electrical GroupThe program tries to load one device after the other. The list will help you to see the progress
35Eaton RF-System© 2013 Eaton Electrical GroupAll devices that must be loaded are additionally displayed as question marks , but keeps theirname. Aft
36 Eaton RF-System - Help© 2013 Eaton Electrical GroupRecalculate Resenders of old Status connections:With this function you can recalculate resenders
37Eaton RF-System© 2013 Eaton Electrical GroupBackground of this function:In earlier MRF versions the old Status message has only been sent by an actu
38 Eaton RF-System - Help© 2013 Eaton Electrical GroupMessage: Shows the message (command, data) as text, e.g.: Double Push-button (right) sends<ON
39Eaton RF-System© 2013 Eaton Electrical GroupTest project1.mrf displays the project names. By selecting the project name, entering a name inthe name
Eaton RF-System - Help4© 2013 Eaton Electrical Group...
40 Eaton RF-System - Help© 2013 Eaton Electrical GroupBy selecting on an existing area and clicking on Rename, an area name can be changed at anytime.
41Eaton RF-System© 2013 Eaton Electrical GroupDevices can be allocated to an area by using drag & drop or the function Assign topology in thepop-u
42 Eaton RF-System - Help© 2013 Eaton Electrical Groupconnections established.A connection that was established using manual routing will always be di
43Eaton RF-System© 2013 Eaton Electrical GroupTransfer virtual device functionsWith this function you can transfer all the settings and connections of
44 Eaton RF-System - Help© 2013 Eaton Electrical GroupAs a result, both devices will be linked with one another, removed from their respective lists,
45Eaton RF-System© 2013 Eaton Electrical GroupThe real devices have now been assigned the functions of the virtual devices. They must beloaded togethe
46 Eaton RF-System - Help© 2013 Eaton Electrical GroupGo OnlineWith this command you can set up a connection to the Gateway (RS232 interface orUSB-RF-
47Eaton RF-System© 2013 Eaton Electrical GroupToolbar StandardShows the standard tool barToolbar LargeShows the large tool barZoom 100%Zooms the works
48 Eaton RF-System - Help© 2013 Eaton Electrical GroupEinfügen eines Geräts mittels Barcode-ScanScan: Scans all devices in the vicinity.Scan reception
49Eaton RF-System© 2013 Eaton Electrical GroupIn the areas right of the status bar you will see which of the following keys are locked:Display Descrip
5Contents© 2013 Eaton Electrical Group...
50 Eaton RF-System - Help© 2013 Eaton Electrical GroupTopology function.It offers the option of selecting individual areas (left-click). When a specif
51Eaton RF-System© 2013 Eaton Electrical GroupBackground graficThis function shows/hides the background grafic, if one is available.The display of the
52 Eaton RF-System - Help© 2013 Eaton Electrical GroupShow all ConnectionsDisplays all the connections or assignments of all devices carried out in th
53Eaton RF-System© 2013 Eaton Electrical GroupRight clicking such a connection offers the possibility to show status details or to recalculateresender
54 Eaton RF-System - Help© 2013 Eaton Electrical GroupRight clicking on a new status connection will offer the possibility to show the connection path
55Eaton RF-System© 2013 Eaton Electrical GroupUse selection mode to display the reception quality of a specific group.ShortcutsKeyboard: F10To display
56 Eaton RF-System - Help© 2013 Eaton Electrical GroupTemperature InputGatewayHome ManagerAnalog actuatorRoom-ManagerMotion detectorCommunication inte
57Eaton RF-System© 2013 Eaton Electrical GroupThe different setting options are structured as follows:1. The left box displays the sensors assigned to
58 Eaton RF-System - Help© 2013 Eaton Electrical Group5. In this box (bottom right) you can pre-set the behaviour of the transmitter in case of powerr
59Eaton RF-System© 2013 Eaton Electrical GroupOff / Switch-off Delay free selectable for and Off with Advance Warning free selectable for and Push
6 Eaton RF-System - Help© 2013 Eaton Electrical Group Overview Eaton RF-SystemHelp overview:How to startOverview of all devicesSymbols and their meani
60 Eaton RF-System - Help© 2013 Eaton Electrical GroupThe different setting options are structured as follows:1. The left box displays the sensors ass
61Eaton RF-System© 2013 Eaton Electrical GroupBasic Mode). Some functions occupy more than just one command button, as we will see in thefollowing fun
62 Eaton RF-System - Help© 2013 Eaton Electrical GroupOn / Off / Dimming (Standard) ON / OFF / Dim (Brighter) / Dim (Darker), onlyselectable f
63Eaton RF-System© 2013 Eaton Electrical GroupThe shutter actuator can be used for controlling blinds, shutters, awnings, etc. (see Instructions forIn
64 Eaton RF-System - Help© 2013 Eaton Electrical Groupmodifications into the device. Cancel: Discards the modifications carried out and returns to the
65Eaton RF-System© 2013 Eaton Electrical GroupAll functions of a shutter actuator:Shutter (Standard), occupies 4 command buttonsSlat up/down resp. Sto
66 Eaton RF-System - Help© 2013 Eaton Electrical GroupThe actuator is enabled for operation immediately independent form the status of its safetyobjec
67Eaton RF-System© 2013 Eaton Electrical GroupEvery rocker or channel can send the following commands: : short push at the top of the push-button : lo
68 Eaton RF-System - Help© 2013 Eaton Electrical GroupConfiguration window 2-fold pushbutton:Configuration window 4-fold pushbutton:
69Eaton RF-System© 2013 Eaton Electrical GroupBinary Input With binary inputs we basically distinguish between battery-supplied and mains-suppl
7Eaton RF-System© 2013 Eaton Electrical GroupIt is no longer possible to use datapoints of intelligent devices as outputs in the connectionwizard if t
70 Eaton RF-System - Help© 2013 Eaton Electrical Grouppush at the push-button and a long push at the push-button .Mode 2:In this mode both inputs (
71Eaton RF-System© 2013 Eaton Electrical Group1. In the Mode selection box you can set the individual modes (1 to 4) 2. The box top right contains the
72 Eaton RF-System - Help© 2013 Eaton Electrical GroupFor the relevant switching contacts (A and B) you can select whether or not the status is to be
73Eaton RF-System© 2013 Eaton Electrical GroupFor a battery-supplied binary input you can also select how it should behave when the switchingcontact o
74 Eaton RF-System - Help© 2013 Eaton Electrical GroupIn this mode a switching command is sent. The following criteria determine when it is to be sent
75Eaton RF-System© 2013 Eaton Electrical Groupwhether it is to be sent according to a cycle time (to be adjusted with a slider control).Room controlle
76 Eaton RF-System - Help© 2013 Eaton Electrical GroupIn this mode a switching command is sent. It depends on the following criteria at what time it i
77Eaton RF-System© 2013 Eaton Electrical GroupSelecting Send temperature value sends the temperature measured to the Home Manager.You can select how
78 Eaton RF-System - Help© 2013 Eaton Electrical GroupOpen the Folder „Universal Serial Bus Controllers -> Double click every single „USB Root Hub“
79Eaton RF-System© 2013 Eaton Electrical GroupWith that option you assure that the USB-port cannot unintentionally be switched off by the system.Furth
8 Eaton RF-System - Help© 2013 Eaton Electrical GroupMulti-Heating actuator will be supported, a new mains supplied device that can be used tocontrol
80 Eaton RF-System - Help© 2013 Eaton Electrical GroupFor further information on the configuration of the Home Manager, please turn to the Help sectio
81Eaton RF-System© 2013 Eaton Electrical GroupThe different setting options are structured as follows:1. The left box displays the sensors assigned to
82 Eaton RF-System - Help© 2013 Eaton Electrical GroupAmong them, depending on the functions that are set, several slider controls (control time,runti
83Eaton RF-System© 2013 Eaton Electrical Groupselectable for On / Switch-on Delay free selectable for , , and Off / Switch-off Delay free select
84 Eaton RF-System - Help© 2013 Eaton Electrical Grouppushbutton. The assignment to other devices is equal to a pushbutton.2. A ring shaped sensor are
85Eaton RF-System© 2013 Eaton Electrical GroupIn the MRF it is possible to define if a main page (Exception: General) will be visualised on theRoom-Ma
86 Eaton RF-System - Help© 2013 Eaton Electrical GroupShading: The state of the assigned shutters/shutter groups are displayed and canalso be operated
87Eaton RF-System© 2013 Eaton Electrical GroupHeating and cooling with the Room Manager (Room 1 to 3)You can define up to 6 rooms/temperature zones fo
88 Eaton RF-System - Help© 2013 Eaton Electrical GroupMore info about timer programmes you can find here.If you are using both heating and cooling for
89Eaton RF-System© 2013 Eaton Electrical GroupConnection to a Multi-Heating actuator:A Multi-Heating actuator can be connected with its 12 heating inp
9Eaton RF-System© 2013 Eaton Electrical GroupThe message „X devices with incompatible version have been found“ will no longer bedisplayed for devices
90 Eaton RF-System - Help© 2013 Eaton Electrical GroupMulti-Heating actuator as heating request:In this configuration the connected channel of the Mul
91Eaton RF-System© 2013 Eaton Electrical GroupactuatorMulti-Heating actuator as Heating-/Cooling-request:In this configuration the connected channel o
92 Eaton RF-System - Help© 2013 Eaton Electrical GroupAlso see Overview of the Room ManagerVentilation control with the Room ManagerOne or more actuat
93Eaton RF-System© 2013 Eaton Electrical GroupAlso see Overview of the Room ManagerInputs and the Room ManagerUp to 10 different inputs can be defined
94 Eaton RF-System - Help© 2013 Eaton Electrical GroupAlso see Overview of the Room ManagerShading and the Room ManagerYou can define up to 3 groups f
95Eaton RF-System© 2013 Eaton Electrical GroupAlso see Overview Room ManagerOperation-Mode and –Type toggle of the Room-ManagerThe Room-Manager has 2
96 Eaton RF-System - Help© 2013 Eaton Electrical GroupThe operation mode (Automatic, Comfort, Standby, Night, Frost-/Heat protection, OFF) and theoper
97Eaton RF-System© 2013 Eaton Electrical GroupTimers and the Room ManagerUp to 3 different timers can be defined in the Room Manager that can be assig
98 Eaton RF-System - Help© 2013 Eaton Electrical GroupInformation about how to set the timer programme can be found hereAlso see Overview of the Room
99Eaton RF-System© 2013 Eaton Electrical GroupAlso see Overview of the Room ManagerPresence simulation and the Room ManagerWith the presence simulatio
Comments to this Manuals