Eaton POWERWARE 9315 User Manual Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 14
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
www.powerware.com 1.800.356.5794
7
Advanced System Transfer Solutions
Powerware Hot Sync Redundant/Capacity configurations have
become even more important in the development of dual path
power distribution systems for critical data centers. As the quest
for higher levels of availability of protected power at the load
becomes more intense, each critical power path demands the
higher reliability of the Powerware product line gained by removing
cabling, connections, and components from the module topologies.
Powerware Hot-Tie™ Technology
Hot-Tie enables the user of a dual path UPS to transfer all the loads
of one distribution path from one UPS to the other in order to iso-
late the system for growth, maintenance, or repair. The Hot-Tie
circuit momentarily ties the two systems together and then opens
the isolation breaker in the desired path. Work can proceed on the
down system while the other UPS carries the total load. The critical
distribution paths to the load are not deactivated and Static Transfer
Switches are not required to change state. Hot-Tie technology cou-
pled with Powerware Hot Sync Technology provides the user with
even greater levels of redundancy and protection.
Powerware Sync Control Technology
Powerware Sync Control ensures that the output of two (or more)
separate UPS systems (single module or parallel systems) remain in
phase with one another so that Static Transfer Switches connected
between the separate distribution paths may change state seam-
lessly when necessary, or so that a Powerware Hot-Tie system may
be activated to transfer entire loads from one system to another.
Powerware Static Auto Tie
In order to make the semi-automatic Powerware Hot-Tie Technology
fully automatic so that full system load transfers can be made
autonomously, the Powerware Static Auto Tie (SAT) system was
developed. The Powerware SAT system adds a wrap-around static
switch to the tie breaker in the Powerware Hot-Tie system, and then
adds intelligent controls so that a power protection system made
up of two or more separate UPS systems can automatically transfer
entire loads in the event of traumatic, catastrophic failure of one
system…a rare but costly circumstance.
Generator
PDU
PDU
PDU
PDU
PDU
STS
AT
S
Batteries
UPS
UPS
ATS
AUTO TIE
SISSIS
Static Switch
Auxiliary
Generator
Bus
SBM
SBM
Auto
Auto Tie Controls
ATS
TIE
Single PowerCord LoadsSingle PowerCord Loads
Utility Source A
Utility Source B
Auxiliary
Generator
Bus
Dual Power
Cord Loads
Fully Deployed - Static Auto Tie System
Page view 6
1 2 3 4 5 6 7 8 9 10 11 12 13 14

Comments to this Manuals

No comments