Other UPS Manufacturers’ Battery Test Methods
• Inconsistent battery test load yields inaccurate battery runtime
estimates
• Other UPS manufacturers use a timer that does not update as
the load changes
DC Expert Battery Test Method
• Consistent testing proactively provides battery runtime
information, accurate to +/-3%
• During a utility outage, battery time remaining automatically
updates with load shedding
• Battery string health determined during periodic testing
• Programmable, automatic monthly testing, any day, any time
• The monthly battery tests perform very light battery discharges,
removing less than 10% of available battery runtime, to ensure
you are always ready for a utility outage
• Light load testing does not impact battery life
• Rectifier does not turn off during battery testing; rectifier shares
load with battery for consistent battery load testing regardless of
inverter load
• Since the rectifier does not turn off, the critical load is never at
risk during battery testing. If a battery should fail during the test
the system will recover 100%.
• DC Expert log stores results of last 30 tests for trending analysis
• Accommodates either valve regulated (“maintenance-free”) or
wet cell batteries
DC Expert
®
Battery Management (200-500 kVA)
DC Expert provides real-time information on battery string health and battery runtime remaining. With this integral feature, you always
know the condition of your battery string. Most importantly, DC Expert allows you to plan for battery maintenance and avoid any unexpect-
ed load losses due to battery deterioration. DC Expert’s battery test method outperforms the competition. Compare its battery test method
to the method used by other manufacturers, and see for yourself how DC Expert’s technique offers the highest level of assurance and
battery runtime accuracy.
Rectifier
During the battery test, the
rectifier regulates DC link
voltage to obtain consistent
battery power discharge
month to month.
• The battery fully supports the inverter load
• As the critical load changes from test to test, so does the
battery load
• Other UPS manufacturers turn off the rectifier to initiate
battery testing
• If the battery fails during testing, the inverter must perform
an emergency transfer to bypass to prevent dropping the
critical load