Other UPS Manufacturers’ Battery Test Methods
Inconsistent battery test load yields inaccurate battery runtime
estimates
Other UPS manufacturers use a timer that does not update as
the load changes
DC Expert Battery Test Method
Consistent testing proactively provides battery runtime
information, accurate to +/-3%
During a utility outage, battery time remaining automatically
updates with load shedding
Battery string health determined during periodic testing
Programmable, automatic monthly testing, any day, any time
The monthly battery tests perform very light battery discharges,
removing less than 10% of available battery runtime, to ensure
you are always ready for a utility outage
Light load testing does not impact battery life
Rectifier does not turn off during battery testing; rectifier shares
load with battery for consistent battery load testing regardless of
inverter load
Since the rectifier does not turn off, the critical load is never at
risk during battery testing. If a battery should fail during the test
the system will recover 100%.
DC Expert log stores results of last 30 tests for trending analysis
Accommodates either valve regulated (“maintenance-free”) or
wet cell batteries
DC Expert
®
Battery Management (200-500 kVA)
DC Expert provides real-time information on battery string health and battery runtime remaining. With this integral feature, you always
know the condition of your battery string. Most importantly, DC Expert allows you to plan for battery maintenance and avoid any unexpect-
ed load losses due to battery deterioration. DC Expert’s battery test method outperforms the competition. Compare its battery test method
to the method used by other manufacturers, and see for yourself how DC Expert’s technique offers the highest level of assurance and
battery runtime accuracy.
Rectifier
Inverter
DC Link
Inv
e
rt
er
By
p
ass
Rectifier
During the battery test, the
rectifier regulates DC link
voltage to obtain consistent
battery power discharge
month to month.
The battery fully supports the inverter load
As the critical load changes from test to test, so does the
battery load
Other UPS manufacturers turn off the rectifier to initiate
battery testing
If the battery fails during testing, the inverter must perform
an emergency transfer to bypass to prevent dropping the
critical load