NOTE:
Callout letter and
map to drawing #164201118−4
,,,
DESCRIPTION:
DATE:
DRAWING NO:
INSTALLATION NOTES
SHEET:
REVISION:
G
164201118−1
3 of 19
020604
Customer Information
A−4
EATON Powerware
®
9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com
Table C. INPUT/OUTPUT Ratings & External Wiring Requirements for Powerware 9315 400 (0.9 pF)
Ratings
Units Rating 50/60 Hz
Basic unit rating at
0.9 lagging pF load
kVA
kW
300
270
400
360
INPUT/OUTPUT
VOLTAGE
400 400
AC
INPUT
AC Input to UPS Rectifier (0.95min. pF)
3O, 1 gnd
Minimum conductor size (number per O)
Minimum conductor size (number per O
With Filter:
Amps* 536 715
AWG or kcmil(ea) 4/0(3) 350(3)
Without Filter:
Amps* 613 800
AWG or kcmil(ea) 250(3) 400(3)
*(Maximum amps includes full load current plus
battery recharge current)
AC
INPUT
AC Input to Bypass
Full Load Current 3O, (1) Neutral, (1) gnd
Minimum conductor size (number per O)
Amps 433 577
AWG or kcmil(ea) 3/0(3) 250(3)
DC
INPUT
DC Input from Battery to UPS
(1) positive, (1) negative
Minimum conductor size (number per O)
VDC
Amps @ (1.8V/cell)
420
772
420
1030
AWG or kcmil(ea) See
Table E
See
Table E
AC
OUTPUT
AC Output to Critical Load
Full Load Current 3O, (1) Neutral, (1) gnd
Minimum conductor size (number per O)
Amps 433 577
AWG or kcmil(ea) 3/0(3) 250(3)