Getting Started
2−2
EATON Powerware
®
9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com
2.1 Preparing Your Site
For your UPS system to operate at peak efficiency, the installation site should meet the
environmental specifications outlined in the Powerware 9315 (300–500 kVA) UPS Operation
Manual. If you intend to operate the UPS at an altitude higher than 1500m (5000 ft),
contact your service representative for important information about high altitude
operation. The operating environment must meet the size and weight requirements shown
in Table N on page A−15.
The basic environmental requirements for operation of the UPS system are:
A Ambient Temperature Range: 0–40°C (32–104°F)
A Recommended Operating Range: 20–25°C (68–77°F)
A Maximum Relative Humidity: 95%
The UPS and input transformer cabinets use forced air cooling to regulate internal
component temperature. The battery and optional component cabinets use convection
cooling to regulate internal component temperature. Air inlets are in the front of the
cabinet, and outlets are in the top. You must allow clearance in front of and above each
cabinet for proper air circulation.
2.2 Environment Considerations
The life of the UPS system is adversely affected if the installation does not meet the
following guidelines:
1. The UPS system must be installed on a sealed concrete pad on a sealed concrete
floor.
2. The UPS system must be installed in a temperature-controlled indoor area free of
conductive contaminants.
2.3 Preparing for Wiring the UPS System
For external wiring requirements, including the minimum AWG size of external wiring, see
Table A through Table G beginning on page A−2. The power wiring connections for this
equipment are rated at 90°C (194°F). If the ambient temperature is greater than 30°C
(86°F), a higher temperature and/or larger size wire may be necessary. Wiring for optional
accessories (such as a Remote Monitor Panel or Relay Interface Module) should be
installed through the knockout in the bottom of the UPS cabinet. The top entry connection
requires installation of 13 mm (0.5) flexible conduit within the UPS. Bottom entry
connection requires no additional routing of conduit within the UPS.