Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.com/powerquality 9-1
Chapter 9 Product Specifications
9.1 Model Numbers
The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in
50 or 60 Hz with various output power ratings.
9.2 Specifications
The following sections detail the input, output, environmental, and battery specifications for the UPS.
9.2.1 UPS Input
Models Power Rating Frequency
Eaton 9E–20 20 kVA 50/60 Hz
Eaton 9E–30/20 20 kVA 50/60 Hz
Eaton 9E–30/30 30 kVA 50/60 Hz
Operating Input Voltage 208/220 Vac
Operating Input Frequency Range 50/60 Hz
Operating Input Current See Table 3-4.
Reduced for Generator
Adjustable
Input Current Harmonic Content 5% THD at full load
Power Factor Minimum 0.99
Line Surges 4 kV OC, 3 kA SC per ANSI 62.41 and IEC 8014
Battery Voltage 216 Vdc
Battery Charging Capacity 12A maximum at any load up to100% load