Eaton 93E Specifications Page 41

  • Download
  • Add to my manuals
  • Print
  • Page
    / 72
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 40
41
www.eaton.com/powerquality 1300 UPS UPS
Premier series 9 scalable UPS
Part Numbers MX Frame 15 000 MX Frame 20 000
Eaton MX Tower or rack-mounting: standard backup time MXF15KC05 MXF20KC05
Eaton MX EXB: battery extension module M87103
Eaton MX / EXB Rack Kit: rail kit for 19” rack mounting M68002
MX 1,8 m Battery extension cable M68528 M68528
MX Battery / Power electronics sub-module M68524 / M68523 M68524 / M68523
Eaton MX Frame empty chassis M68526 M68526
Battery Integration System (up to 9 EXB) M68527 M68527
1: (with rack kit, casters, NMC card) MXF15KC05 = M68526 (empty Eaton MX Frame) + 3 x M68524 + 3 x M68523. 2: (with rack kit, casters, NMC card) MXF20KC05 = M68526 (empty Eaton MX Frame) + 4 x M68524 + 4 x M68523.
Eaton MX Technical Specifications MX Frame 15 000 MX Frame 20 000
Rating (kVA/kW) 15 kVA / 13.5 kW 20 kVA / 18 kW
Paralleling
Maximum rating / redundancy
(1)
15 kVA / 10 kVA + 5 kVA redundancy
5 kVA + 2 x 5 kVA redundancy
20 kVA / 15 kVA + 5 kVA redundancy
10 kVA + 2 x 5 kVA redundancy
Inputs
Technology VFI-SS-113, on-line double conversion with power factor correction, convection cooled static bypass switch
Number of phases, input connections L + N or 3P + N, terminals up to 35 mm
2
, separate or common AC normal and AC bypass
Nominal voltage 200/208/220/230/240/250 V (L + N) or 380/400/415 V (3P + N)
Voltage range without using battery
(2)
120 - 280 V (L + N), 250 - 465 V (3P + N)
Input frequency range, THDI 40-70 Hz, < 7%
Outputs
Output connections
(3)
Terminals + 8 x IEC C13 (10A) + 4 IEC C19 (16A), sockets, except on -HWOP models
Remotely controlled Powershare sockets 2 groups (2 IEC C13 10A per group)
Output voltage and frequency
(4)
, THDU, efficiency
(5)
200/208/230/240 /250 V, 50 / 60 Hz autoselect, frequency converter as standard, < 2%, 97%
Backup time
(6)
Eaton MX standard backup time 8 minutes 8 minutes
Eaton MX + EXB / MX + 2 EXB / MX + 3 EXB 35 min (3 EXB)/60 min (6 EXB)
/90 min (9 EXB)
(7)
35 min (4 EXB)/60 min (8 EXB)
/90 min (12 EXB)
Communications
Slots
1 Mini Slot (MX) or 2 Mini Slot (MX Frame) for Network Card-MS, Relay Card-MS or Network & Modbus Card-MS
connectivity cards
Ports
Remote Power off (RJ11), 5 output contacts (DB9), setup via Solution-Pac
(8)
, (USB and DB9-serial ports), EXB detection (RJ45),
paralleling (DB 15)
Operating conditions, standards and approvals
Performance, safety, EMC, surge protection IEC/EN 62 040-3, IEC/EN 62 040-1-1, IEC/EN 62 040-2 class A (class B as option), 4 kV IEC 61 643, UL 1778 and CSA 22.2
(9)
Operating temperature, noise, approvals, guarantee 0°C to 40°C continuous, 45 dbA
(10)
, UL, TüV, GS mark, CB, C-Tick, CE, IEC 61 931, one year
(11)
Dimensions H x W x D / Weight
Eaton MX standard backup tower Tower 690 mm high (795 mm casters) x 444.5 mm wide x 735 mm deep / 250 kg
Eaton MX standard backup rack Rack 16U x 444.5 mm wide, compatible with 800-1000 mm deep rack
Eaton MX EXB battery unit tower / rack Dimensions same as MX Frame / 194 kg for 15 kVA, 239 kg for 20 kVA
Customer Service & Support
Warranty 2 year warranty, including batteries.
1: Eaton MXs can be paralleled using ModularEasy. 2: At 70% load. 3: 4 IEC C13 (10A) 2 m long cables for use with retention clips (8 cables for use with Eaton MX Frame). 4: Frequency conversion for non-paralleled units only.
5: Economy mode, 91% in normal mode. 6: At 70% nominal rating with power factor 0.7 typical values after 3 charge/discharge cycles, with 3-5 years old batteries. Weekly battery test without interrupting the load (daily or monthly if
required). EXB compatible with 0.8 power factor loads. 7: With Eaton MX Frame EXB (4 battery units). 8: Solution-Pac CD-ROM supplied as standard. 9: Applicable to US models. 10: 50 dbA above 5 kVA. 11: Depending on the country,
see www.eaton.com/powerquality.
Page view 40