Using Features and Options
6−2
EATON Powerware
®
9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com
6.2 Summary Alarm Contacts
Two summary alarm contacts are provided as a standard feature on the UPS. The alarm
contacts (one notice and one alarm) are located inside the UPS on the customer interface
panel (see Figure 6-2).
NOTICE NO
NOTICE NC
COMMON
ALARM NO
ALARM NC
COMMON
10
11
12
13
14
15
TB2
Figure 6-2. Summary Alarm Contacts
You can specify that each contact be either normally closed (NC) or normally open (NO). If
the state of the contact changes from the state you specify as normal, an alarm is issued.
You can connect these contacts to equipment at your facility (such as a light or an alarm
bell) to let you know when an alarm is active on the UPS. This feature is useful if the UPS is
located in a remote area where the UPS alarm horn may not be heard immediately.
C A U T I O N
Contacts should not be operated in excess of 30 Vac or 42.4V peak AC or DC @ 1A maximum.