Volume 3—Power Distribution and Control Assemblies CA08100004E—November 2013 www.eaton.com V3-T9-51
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.3
Metering Devices, Protective Relays, Software and Connectivity
Metering Devices
Displayed Information
Monitored information is
available locally through the
display, the Web browser
or system power
management software
True rms values through
40th harmonic
ANSI C12.20 Class.2%
revenue metering
specification
Power Xpert 2000 Web Browser Views
Power Xpert Meter 2000 Web Browser
Power Xpert Meter 2000’s
embedded Web server offers
Eaton customers a new level
of accessibility to the critical
information required to
manage the electrical
distribution system. The
embedded Web server
includes real time circuit
information in both numeric
and graphical formats to help
monitor parameters such as
current loading, voltage and
power levels and power
factor. The Web server also
provides the energy and
demand readings required to
help manage the cost of
energy. Readings include
kWh, kVARh, delivered and
received and kVAh. The Web
server also includes critical
information regarding power
quality such as harmonic
distortion.
Real-Time Visualization of Harmonic
Content
The Web server offers a
waveform view to visualize
steady-state harmonic
content of the voltage
and current to spot power
quality problems.
Harmonic Spectral Plot
The harmonic spectral plot
displays harmonics up to the
40th order. A detailed table
also includes individual
magnitudes and angles of
current and voltage
harmonics, at each
frequency. Individual and
total THD are displayed for
diagnostic purposes.
Historical Trend Plot
Graphical Trending of Data
The Power Xpert Meter 2000
embedded Web server
supports graphical trend
charts of key circuit
measurements such as
current, voltage, power and
energy. The trend chart
supports a zoom feature
that allows the user to view
data over a short period of
16 hours or a longer period of
48 months. The trend chart
has a horizontal slider bar
control to manage scrolling
forward and backward
through the data. Trend
charts of basic readings
include minimum, maximum
and average readings. Trend
charts of energy data also
display demand values.
Energy Demand Profile
Energy managers can view
load profile data compared
against the peak demand.
The plot allows comparison
of present and past months’
usage.
Web Server Device
Configuration
Special software is not
required to configure a
Power Xpert Meter 2000.
The embedded Web server
includes a comprehensive
device configuration engine.
Discrete Contact Inputs
The optional I/O expansion
cards offers two or four
digital inputs that are useful
for a variety of applications
such as:
Pulse counting of KYZ or
other utility pulses such as
air, water or gas
Demand interval timing
taken from a master utility
meter end of interval pulse
Names can be configured for
each input for ease of use.