Metering Devices, Protective Relays, Software and Connectivity
Protective Relays
EDR-3000
Contents
Description Page
Product Selection Guide . . . . . . . . . . . . . . . . . . . . V3-T9-158
FP-6000 Feeder Protection . . . . . . . . . . . . . . . . . . V3-T9-162
FP-5000 Feeder Protection . . . . . . . . . . . . . . . . . . V3-T9-172
FP-4000 Feeder Protection . . . . . . . . . . . . . . . . . . V3-T9-180
MP-3000 Motor Protection . . . . . . . . . . . . . . . . . . V3-T9-188
MP-4000 Motor Protection . . . . . . . . . . . . . . . . . . V3-T9-198
MD-3000 Motor/Generator Differential Relay . . . . V3-T9-204
Digitrip 3000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V3-T9-207
VR-300 Multifunctional Voltage Relay . . . . . . . . . . V3-T9-217
DP-300 Current Differential Protection Relay . . . . . V3-T9-221
EDR-3000 Feeder Protection
Features, Benefits and Functions . . . . . . . . . . . V3-T9-228
Standards and Certifications . . . . . . . . . . . . . . . V3-T9-228
Catalog Number Selection . . . . . . . . . . . . . . . . V3-T9-229
Technical Data and Specifications . . . . . . . . . . . V3-T9-230
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . V3-T9-235
ETR-4000 Transformer Protection Relay . . . . . . . . V3-T9-237
Ground Fault Relay . . . . . . . . . . . . . . . . . . . . . . . . . V3-T9-250
Universal RTD Module . . . . . . . . . . . . . . . . . . . . . . V3-T9-254
IQ 125 Volt DC Power Supply. . . . . . . . . . . . . . . . . V3-T9-258
EDR-3000 Feeder Protection
Product Description
The EDR-3000 Protective
Relay is a multifunction,
microprocessor-based
overcurrent relay designed
for both ANSI and IEC
applications. It is a panel-
mounted, self-contained unit
that operates from either AC
or DC control power. The
EDR-3000 design provides
true rms and fundamental
sensing of each phase and
ground current. Only one unit
is required for each three-
phase circuit.
Current monitoring and
operator selectable protective
functions are integral to each
relay. The EDR-3000 relay
operates from the 5A or 1A
secondary output of standard
current transformers. Current
transformer ratio information
is quickly programmed into
the unit via settings. This
enables the relay to display
metered current in primary
amperes, secondary amperes
or per unit values. The EDR-
3000 features a user-friendly
operations panel to monitor
and program the relay.
Operating parameters and
troubleshooting information
are displayed in the 128 x 64
LCD. In addition, all data and
information can be
communicated to a host
computer equipped
with PowerPort-E™.
A “Communication Trip” and
“Communication Close”
control command can also be
initiated by a host computer
with an authorized access
code for remote breaker
operation.
Application Description
The EDR-3000
microprocessor-based relay
provides reliable three-phase
and ground overcurrent
protection for all voltage
levels. It can be used for
any application where
instantaneous and/or time
overcurrent protection is
required. It is most commonly
used as primary feeder circuit
protection, shown below.
Primary Feeder Circuit
Protection
The EDR-3000 may be
applied as the transformer
primary protection or as
backup to the differential
protection, see below.
Transformer Overcurrent
Protection
The EDR-3000 may be
connected to the secondary
side of a delta-wye grounded
transformer with the ground
element connected to a
separate CT in the neutral
connection of the
transformer. With this
connection, a lower CT
ratio and a pickup setting
can be used to provide
more sensitive ground fault
protection especially for
resistance grounded
systems, shown below.
Transformer Secondary
Protection with Neutral CT
Connection
The EDR-3000 relay has
special provisions for
connection in a Zone
Interlocking scheme that can
be used for bus protection
or to improve protection
coordination in a tight or close
system. Zone Interlocking
is described in following
sections. In addition the
EDR-3000 has multiple
setting groups that can be
used to reduce arc flash
hazard with instantaneous
elements.
Residual Ground Connection
50 51
50G 51G
CB
52
EDR-3000
Load
50 51
50G 51G
CB
EDR-3000
50G 51G
50 51
EDR-3000
Resistor
CB
a
b
c
GND
EDR-3000
CB-52
23
56
89
12 11
50N/51N
50/51