Volume 3—Power Distribution and Control Assemblies CA08100004E—November 2013 www.eaton.com V3-T9-105
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.3
Metering Devices, Protective Relays, Software and Connectivity
Metering Devices
PXMP meter modules (PXMP-MMs)
Compatible with all PXMP Meter Base slots 1–10 LED
indicators:
●
Health and status green, blink to show activity
●
Pulse energy output one red per group of three loads
●
Load energy direction red/green pair per load
All variations support six load inputs.
Current sensor connection is one 2 x 2 connector per load.
Compatible with PXMP-SCXX sensor cables, total cable length
to the sensor should not exceed 28 ft (8.5m).
Note that -AB suffix only affects what voltage channels the loads
are paired with for metering purposes.
PXMP-MM10MA supports the CSXXX series of 10 mA
maximum secondary output current transformers.
PXMP-MM100MA supports the PXMP-CSXXX series of 100 mA
maximum secondary output current transformers.
PXMP-MM333MV supports 333 mV maximum secondary
output current transformers with the use of the PXMP-
IM333MV interface module.
PXMP digital output module (PXMP-DOM)
●
Compatible with all PXMP-MB slots 1–10
●
LED indicators
●
Health and status green, blink to show activity
●
Output On/Off status one green per output
●
Eight individual solid-state relay outputs
●
Each circuit rated for 24 Vdc (±20%) with an 80 mA load
maximum
●
24 Vdc is externally sourced
●
Group isolation to ground 2 kV
●
Each circuit has its own separate common, circuit-to-circuit
isolation 120V
●
16-position removable terminal plug
●
12–18 AWG (3.31–0.82 mm
2
), wire ferrules recommended
PXMP pulse input modules (PXMP-PIMs)
●
Compatible with all PXMP-MB slots 1–10
●
LED indicators
●
Health and status green, blink to show activity
●
Input On/Off status one green per pulse input
●
Eight pulse inputs to external dry contacts
●
Maximum pulse rate is 20 Hz
●
Minimum pulse width is 20 milliseconds
●
External circuit groups rated for 24 Vdc (±20%)
●
All circuits share the same electrical common
●
External supply connects to the module with a two-position
removable terminal plug
●
The supply is internally fanned out to all circuits
●
Group isolation limited to 300V to ground due to TVS diode
clamp
●
Input impedance ~2.2K causing a 10 mA load per input when
energized
●
External circuit groups connect with a 16-position removable
terminal plug
●
Terminals support 12–18 AWG (3.31–0.82 mm
2
), wire
ferrules recommended
PXMP energy portal module (PXMP-EPM)
●
Only functionally compatible with PXMP-MB slot 10
●
LED indicators
●
Top health and status green, blink to show activity
●
Com. reset button—reset to defaults
●
Local IP 192/10
●
RJ45 front-facing Ethernet configuration port LEDs
– Link (Tx/Rx blink)
– 10/100 speed
●
LED four-stack for bottom LAN/WAN Ethernet port
●
Link (Tx/Rx blink)
●
10/100 speed
●
DHCP/Fixed
●
TX active
●
Config. Ethernet RJ45 Cat5 STP/UTP
●
10Base-T/100Base-Tx
●
Auto crossover capability supported
●
Java Web browser interface
●
Bottom facing LAN/WAN Ethernet port
●
RJ45 Cat5 STP/UTP 10Base-T/100Base-Tx
●
STP required for full electromagnetic immunity
●
Auto crossover capability supported
●
Supports Modbus TCP and Java Web browser interface
●
Bottom-facing telephone modem interface
●
Modem type V92/56K baud
●
RJ11 field interface