Eaton TBL-100K-6 Datasheet Page 2

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 1
Technology Tap changer
Input voltage range +10% to -20%
Output voltage range ±3% typical
Input frequency range 47-53 Hz for 50 Hz models, 57-73 Hz for 60 Hz models
Efficiency 97% typical, 95% minimum
Load power factor 0.6 leading to 0.6 lagging
Common-mode noise attenuation 140 dB
Normal-mode noise attenuation -3 dB @ 1000 Hz, -40 dBA per decade
Total harmonic distortion Less than 1% added
Correction time 1 cycle typical, 1.5 cycle maximum
Overload rating 200% for 10 seconds, 1000% for 1 cycle
Overvoltage protection Automatic electronic shutdown if output voltage exceeds +10% for 6 seconds (adjustable)
EnvironmEnts
Indicator lights Three green lights indicate regulated voltage on each phase. A fourth red light indicates an overtemperature condition
Audible noise Less than 50 dBA @1 meter (depending on size)
Operating temperature -10°C to +40°C
Altitude Up to 10,000 ft
standards
Safety agency UL 1012, CSA, FCC Cat. A
Surge suppression Meets ANSI/IEEE Standard C62.41-1991
Warranty One year
*Due to continuing product improvement programs, specifications are subject to change without notice.
UNITED STATES
8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.800.356.5794
www.eaton.com/powerquality
CANADA
Ontario: 416.798.0112
LATIN AMERICA
Brazil: 55.11.3616.8500
Caribbean: 1.949.452.9610
México & Central America:
52.55.9000.5252
South Cone: 54.11.4343.6323
EUROPE/MIDDLE EAST/AFRICA
Denmark: 45.3686.7910
Finland: 358.94.52.661
France: 33.1.6012.7400
Germany: 49.0.7841.604.0
Italy: 39.02.66.04.05.40
Norway: 47.23.03.65.50
Portugal: 55.11.3616.8500
Sweden: 46.8.598.940.00
United Kingdom: 44.1753.608.700
ASIA PACIFIC
Australia/NZ: 61.2.9693.9366
China: 86.21.6361.5599
HK/Korea/Taiwan: 852.2745.6682
India: 91.11.4223.2300
Singapore/SEA: 65.6829.8888
Eaton, Power-Sure and PowerChain
Management are tradenames, trademarks
and/or service marks of Eaton Corporation.
All other trademarks are the property
of their respective owners.
©2009 Eaton Corporation
All Rights Reserved
Printed in USA
POWSR700FXA
July 2009
tEchnical spEcifications*
powEr-surE 700 powEr conditionErs (thrEE-phasE)
Part Number kVA Input voltage Output voltage
Output
distribution
Cabinet size
(H x W x D, in) Weight (lb)
T_ _-010k-_ 10 208/240/480 208Y/120 Hardwire 30.0 x 21.5 x 29.0 440
T_ _-015k-_ 15 208/240/480 208Y/120 Hardwire 30.0 x 21.5 x 29.0 520
T_ _-025k-_ 25 208/240/480/600 208Y/120 Hardwire 44.0 x 21.5 x 29.0 700
T_ _-030k-_ 30 208/240/480/600 208Y/120 Hardwire 44.0 x 21.5 x 29.0 720
T_ _-045k-_ 45 208/240/480/600 208Y/120 Hardwire 44.0 x 45.0 x 29.0 950
T_ _-050k-_ 50 208/240/480/600 208/120-480/277 Hardwire 44.0 x 45.0 x 29.0 970
T_ _-075k-_ 75 480/600 208/120-480/277 Hardwire 44.0 x 45.0 x 29.0 1100
T_ _-100k-_ 100 480/600 208/120-480/277 Hardwire 44.0 x 45.0 x 29.0 1660
T_ _-125k-_ 125 480/600 208/120-480/277 Hardwire 44.0 x 45.0 x 29.0 1980
T_ _-150k-_ 150 480/600 208/120-480/277 Hardwire 44.0 x 45.0 x 29.0 2200
T_ _-225k-_ 225 480/600 208/120-480/277 Hardwire 77.0 x 56.0 x 41.5 3300
T_ _-300k-_ 300 480/600 208/120-480/277 Hardwire 77.0 x 56.0 x 41.5 4000
®
®
Part #T__ __ - 010k - __
Input options
B=208 Vac, C=240 Vac,
D=480 Vac, E=600 Vac
Output options
L=208/120 Vac (wye) output
N=480/277 Vac (wye) output
Frequency rating
6=60 Hz; 5=50 Hz
75–300 kVA are available with 480/600V input only; requires
an additional auto-transformer for lower input voltage
Listings - UL listed, CSA Certified, except for 600V: no UL,
CSA on 600V units
For output distribution option, call factory
• K factor rated units available on request
Page view 1
1 2

Comments to this Manuals

No comments