Features
Processor controlled voltage regulation
Tight output voltage regulation
Zero-current switching
Wide input regulation range
Triple shielded, computer grade transformer
Highly efficient —97 percent typical
High inrush capability
Transient protection and high frequency filter
Over/under voltage protection (optional)
Includes input circuit breaker
Manual bypass switch (optional)
Pulsar series
Eaton Power-Sure 700
Intelligent protection for transmitters & industrial controls
The Eaton
®
Power-Sure
TM
700 three-phase power line conditioning
system provides exceptional system reliability that can be
attributed to Eaton’s processor-controlled zero-current cross tap
switching technology.
The Power-Sure 700 combines voltage regulation with a
transformer and filter to remove transients and noise. The
combined effect is a regulating and shielded isolation transformer/
system that solves 99 percent of the electrical disturbance
problems, including electrical brownouts, sags, surges, transients
and other electrical disturbances.
This state-of-the-art power conditioner also provides the protection,
efficiency and reliability that are critical to every application with
sensitive equipment.
10–300 kVA
Options
RRM2020—Regulation Range Monitor has above, below and
normal LED indicator lights that indicate when the input is beyond
the regulation range or within the range.
RBS202x—Integral Manual Rotary Maintenance Bypass Switch
Specic models numbers include:
RBS2020 - 10 to 15 kVA units
RBS2021 - 25 to 30 kVA units
RBS2022 - 45 to 125 kVA units
RBS2023 - 150 kVA units
RBS2024 - 225 to 300 kVA units
REP2020—Remote Emergency Power Off Option (REPO)—a
remotely mounted pushbutton is provided with 50 feet of cable.
The Shunt Trip option, STC2020, is required with this option.
STC2020—Shunt Trip for Main Circuit Breaker Option.
UOV2020—Under/Over Voltage Shutdown Option—if the output
exceeds preset values, the unit output will shut off electronically
& illuminate a diagnostic light.
PSO2020—Under/Over Voltage Shutdown with Loss of Power Shut
Off—instead of disabling the output, this option will shunt trip the
main circuit breaker if the output voltage exceeds preset values.
The Shunt Trip option, STC2020, is required with this option.
ERR1040—Extended Regulation Range Option—provides +10%
to - 40% input regulation range for intermittent duty only. Output
regulation is +5% to -6% from nominal with this option.
Page view 0
1 2

Summary of Contents

Page 1 - Eaton Power-Sure 700

Features• Processor controlled voltage regulation• Tight output voltage regulation• Zero-current switching• Wide input regulation range• Triple

Page 2 - Part #T__ __ - 010k - __

Technology Tap changerInput voltage range +10% to -20%Output voltage range ±3% typicalInput frequency range 47-53 Hz for 50 Hz models, 57-73 Hz for 60

Comments to this Manuals

No comments